Control Outputs Configuration (Setting Via Dip Switches 4 / 5 And Parameters P46 / P47) - Siemens RDG100 Basic Documentation

Room thermostats with lcd for wall mounting
Hide thumbs Also See for RDG100:
Table of Contents

Advertisement

Application
2-pipe
2-pipe and electric heater
2-pipe and radiator / floor
heating
4-pipe
4-pipe and electric heater
2 stage, cooling or heating
Available with type 
RDG100, RDG100T,
RDG100T/H
RDG140, RDG160
Note
Siemens
Building Technologies
4.7.2
Control outputs configuration
(setting via DIP switches 4 / 5 and parameters P46 / P47)
Control outputs
With RDG100, RDG100T and RDG100T/H, the function of the control outputs (2-
position or 3-position) is set via DIP switches 4 and 5 .
With RDG140 and RDG160, DIP switches 4 and 5 can be used to invert the
DC 0...10 V signal to 10...0 V.
The patterns of DIP switches 4 and 5 are as follows:
ON
OFF
1
2
3
4
5
Y1 / Y2 =
2-position
Y3 / Y4 =
2-position
Y10 =
DC 0...10 V
Y20 =
DC 0...10 V
RDG100, RDG100T, RDG100T/H:
If 2-position is selected, the factory setting is on/off. If you want PWM (pulse width
modulation), set parameters P46 and / or P47 to 2 = PWM.
RDG110: Only on/off available.
For details concerning connection of peripheral devices and setting of the DIP
switches, refer to the Mounting Instructions:
– [4] M3181.1 (RDG100, RDG100T)
– [5] M3181.2 (RDG110)
– [6] M3181.3 (RDG140, RDG160)
– [7] M3181.4 (RDG100T/H)
RDG100, RDG100T, RDG110, RDG140, RDG160
Functions











ON
ON
OFF
OFF
1
2
3
4
5
2-position
3-position
DC 0 ... 10 V
DC 10 ... 0 V inv.
Basic Documentation








(
) *



* (only possible for 1 actuator)
ON
OFF
1
2
3
4
5
1
3-position
2-position
DC 10 ... 0 V inv.
DC 0 ... 10 V










2
3
4
5
3-position
3-position
10 ... 0 V inv.
10 ... 0 V inv.
23 / 66
CE1P3181en
14 Dec 2011

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdg110Rdg100tRdg160Rdg100t/hRdg140

Table of Contents