Page 1
RDF310.2/MM Flush-mounted Room RDF310.2/MM Thermostat for 2-pipe fan coil units · Output for on/off valve or 3-wire on/off valve actuator · 3-speed fan control: Automatic or manual · Manual heating/cooling changeover or continuous Cooling only / Heating only · Operating modes: Comfort, Protection ·...
Page 2
· Output for 2-position (on/off) valve or 3-wire (on/off) valve actuator Applications Application and output signal, diagram · 2-pipe fan coil unit ON/OFF (heating or cooling) V1 Heating/cooling valve actuator M1 3-speed fan N1 Thermostat 2/14 Siemens Flush-mounted Room Thermostat CB1N3066en Smart Infrastructure 2019-10-25...
P21 “ON in dead zone”. In this case, the fan keeps running at minimum fan speed 1 in the neutral zone. 3/14 Siemens Flush-mounted Room Thermostat CB1N3066en Smart Infrastructure 2019-10-25...
The minimum output on/off time of Y11 and Y12 is fixed at 1 minute. It means that any on/off time Y11 and readjustment of the setpoint or of Heating/Cooling Mode changeover lasts for 1 minute before Y11 and Y12 react. 4/14 Siemens Flush-mounted Room Thermostat CB1N3066en Smart Infrastructure 2019-10-25...
Page 5
0 °C, output Y11 is energized. In all other cases, output Y11 is de-energized until the temperature returns to the measuring range, and then the thermostat resumes Comfort mode. 5/14 Siemens Flush-mounted Room Thermostat CB1N3066en Smart Infrastructure...
ON: Room (or return air) temperature OFF in dead zone Fan control in Comfort mode ON in dead zone 0: Heating only Heating/cooling mode 1: Cooling only 3: Manual 3: Manual H/C changeover 6/14 Siemens Flush-mounted Room Thermostat CB1N3066en Smart Infrastructure 2019-10-25...
Page 7
Thermal actuator STP23... 4884 (for small valves 2.5 mm) Ordering When ordering, please indicate the product name, product number and SSN number: (e.g. room thermostat, RDF310.2/MM, S55770-T187) Valve actuators should be ordered separately. 7/14 Siemens Flush-mounted Room Thermostat CB1N3066en Smart Infrastructure...
European Directive and may not be disposed of as domestic garbage. · Dispose of the device through channels provided for this purpose. · Comply with all local and currently applicable laws and regulations. 9/14 Siemens Flush-mounted Room Thermostat CB1N3066en Smart Infrastructure 2019-10-25...
Page 10
IP 30 as per EN 60529 Housing flammability class according to UL94 The product environmental declaration CB1E3066en contains data on environmentally Environmental compatible product design and assessments (RoHS compliance, materials conditions composition, packaging, environmental benefit, disposal). 10/14 Siemens Flush-mounted Room Thermostat CB1N3066en Smart Infrastructure 2019-10-25...
1 x 0.4-1.5 mm Weight 0.17 kg Color of housing front white, RAL 9003 *) The documents can be downloaded from http://siemens.com/bt/download. No condensation is allowed. Connection terminals L, N Operating voltage AC 230 V Control output “Fan speed 1 AC 230 V Control output “Fan speed 2 AC 230 V...