Before you start 1.3.1 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed only to authorized persons or companies with the required technical knowledge. 1.3.2 Quality assurance This document was prepared with great care.
RDF302 room thermostats in the RS485 Modbus RTU network. Since Modbus protocol has been well known for years in the industry, this document will explain the operations related to RDF302 Modbus units. e.g. the unit setup, available settings and their applications. And, users should have the general knowledge of HVAC systems and local electrical installation regulations where RDF302 units are employed.
Backlit display AC 230 V operating voltage Room temperature control via built-in temperature sensor or external room Functions temperature / return air temperature sensor 7 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Summary 07 Dec 20111...
RS 485 Modbus (terminals +, - and REF) for communication with Modbus compatible devices Integration via Modbus The RDF302 is a communicative thermostat with Modbus open protocol on RTU (Remote Terminal Unit) mode enabling easy integration into BACS via RS-485. The following Modbus functions are available: ...
Plastic mounting bracket for semi-flush-mount thermostats for increasing the headroom in the ARG70.3 N3009 conduit box by 10mm ARG71 / N3009 Conduit box for semi-flush mounted thermostat S55770-T137 9 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Summary 07 Dec 20111...
P07 = 3 or 4. The display format is either in 12- or in 24-hour format. Time of day The information can be received from a master device in the Modbus network. 10 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
– protected against overheating (factory setting OFF, can be enabled or changed via P66) No other operating mode can be selected locally if Protection mode is commanded via Modbus. is displayed. 11 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
Note: Only one input source must be used, either local input X1/X2 or Modbus. User operations are ineffective and “OFF” is displayed if the operating mode switchover contact is active, or if "WindowContact" is sent via Modbus. 12 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
Use control parameters P65 and P66 to adjust the Protection mode setpoints. Protection mode The heating setpoint is factory-set to 8 °C (frost protection) and to OFF for cooling. 13 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
The current setpoint (used by the thermostat for temperature control) is available Room temperature: on the Modbus for use in the central control unit. Current setpoint 14 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
Page 15
Protection setpoint is OFF, then minimum 5 °C and maximum 40 °C are used The resulting setpoints for cooling and heating of the same operating mode have a minimum distance of 0.5 K between them 15 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
All DIP switches need to be set to OFF (remote configuration, factory setting) to select an application via Modbus commissioning tool. The RDF302 offers the applications printed in bold text (basic applications). For universal applications (chilled ceiling, etc.), refer to section 3.6.5.
Page 17
M1 3- or 1-speed fan actuator Y2 Cooling valve actuator B1 Return air temperature sensor or external room temperature sensor (optional) E1 Electric heater B2 Changeover sensor (optional) 17 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
If manual heating / cooling changeover is commissioned (P01 = 2), then heating / cooling mode cannot be changed via changeover sensor / switch; it will remain in the last mode as selected locally via button. 18 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
Page 19
Up to 26 °C for long-time presence, up to 28 °C for short-time presence. Bath rooms: Up to 28 °C for long-time presence, up to 30 °C for short-time presence. 19 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
Page 20
B = Lock operating mode button only C = Lock fan button only D = Lock temperature adjusting buttons (+ & -) only. E = Unlock 20 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
/ cooling sensor or remote switch ("main and secondary" application), see section 3.6.4 For the relation between setpoints and sequences, see section 3.6.7. 21 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Functions 07 Dec 20111...
Note: The diagrams only show the PI thermostat’s proportional part. Setting the sequence and the control outputs Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs". 22 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
If “Enable electric heater” input is used via Modbus, then the function must not be assigned to a local input X1 or X2. Caution An electric heater must always be protected by a safety limit thermostat! 23 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 24
Note: The diagrams only show the PI thermostat’s proportional part. Setting the sequence and the control outputs Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs". 24 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
The thermostat assumes winter operation when B2 > P37 (factory setting 28 °C) The thermostat assumes summer operation when B2 < P36 (factory setting 16 °C) 25 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 26
The diagrams only show the PI thermostat’s proportional part. Note: Setting the sequence and the control outputs Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs". 26 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
= setpoint heating in Economy or Protection mode HeatEco/Prot = setpoint cooling in Economy or Protection mode CoolEco/Prot YR = radiator sequence YE = electric heater sequence 28 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 29
W = setpoint in Comfort mode = heating setpoint for Economy or Protection mode HeatEco/Prot = cooling setpoint for Economy or Protection mode CoolEco/Prot YE = electric heater sequence 29 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
3. After the actuator reaches the position calculated by the thermostat, a waiting time of 30 seconds is applied to stabilize the outputs. 30 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
4-pipe and 2-pipe with electric heater, only have On/Off type of outputs. The application and control output can be changed between On/Off and 3-position Plant type via Modbus. 31 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Switching differential “Heating” Switching differential “Cooling” Dead zone Cool Switching range for fan “Heating” Switching range for fan “Cooling” T[°C] SDH/SDC >4.5 Look-up table with /XpC ON/OFF control 32 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 33
When the fan starts from standstill, it starts at speed 3 for 1 second to ensure safe fan motor start by overcoming inertia and friction (selected via parameter P58). 1 sec 33 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 34
The “Clean fan filter reminder” is reset when the operating mode is manually set to Protection and back. The ‘Clean fan filter reminder’ and error information (see 3.11.1) can be obtained Fault information via Modbus object: Fault information 34 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
X1, X2. See also section 3.2. Dew point monitor Digital input for a dew point sensor to detect condensation. Cooling is stopped if condensation occurs. 35 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
For all other cases, no output is activated. The thermostat resumes Comfort mode after the temperature returns to within the measuring range. For fault status messages on the Modbus, see section 3.11.1. Fault information 36 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
3.11 Modbus RTU mode The RDF302 thermostats support communication protocol (Modbus RTU mode) as per the Modbus specification. (refer to: http://www.modbus.org) Device address The device address range is from 1 to 247. The device address can be changed via parameter P81. (factory setting = 1) Baud rate The available baud rates are 4800 bps, 9600 bps, 19200bps and 38400 bps.
P01 must be set to 2, the manual heating/cooling changeover Either using local input, X1/X2 input, or Modbus command 3 way DipSwitch must be set to OFF-OFF-OFF 38 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
3.12.2 Description of communication objects 39 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 40
40 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 41
41 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 42
{0,1} Standard 1 : Time = UT+X+1 Summer Time 0 : clock without ext. sync signal {0,1} Quality of 1 : clock with ext. sync signal Clock 42 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
3.13.2 Parameter setting / download via Modbus communicatin tool Control parameters can be adjusted via Modbus either by local HMI or Modbus commissioning tools. Please refer to section 4.2 for commissioning. 43 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
2 = Manual lock Note: Parameter P13 and P54 is only displayed for application "2-pipe with electric heater". All temperature settings are in increments of 0.5 °C. 44 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Fan speed switching point low 1...15% Fan start kick ON: Enabled OFF: Disabled Fan minimum on time 2 min 1...6 min Periodic fan kick Comfort 0…89 min, OFF(90) 45 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 46
Press buttons + and – simultaneously to escape. actuator's running direction Parameters d05 will only appear when the application (DIP switch) set to 2 pipe 3 position. 46 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Isolate the cables of Modbus communication input +, - and REF for 230 V. No metal conduits No cables provided with a metal sheath Disconnect from supply before opening the cover 47 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
We recommend to review the setpoints and setpoint ranges (parameters Setpoint and range limitation P08…P12) and change them as needed to achieve maximum comfort and save energy 48 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
+ again >3 seconds level” Press + and – >3 seconds, release, Go to parameter setting mode “Expert then press – again >3 seconds level”, diagnostics and test 49 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
The relevant national legal rules must be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 50 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Slide the front panel in the mounting base and snap on. Operation and settings RDF302 1. Operating mode selector 2. Change fan operation 3. Adjust setpoints and control parameters For operation, refer to section 4.3. 53 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
< ± 0.5 K Accuracy at 25 °C ± 3.0 K Temperature calibration range Settings and display resolution 0.5 °C Setpoints 0.5 °C Current temperature value displayed 55 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Page 56
(Note: For sensors on inputs X1 and X2, the cable length is max. 80 m.) Housing front color RAL 9003 white Weight without / with packaging 0.174 kg/0.261 kg 56 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies 07 Dec 2011...
Switching differential ..........10 Fan start..............33 Synchronization.............30 Fault..............36 Fault on KNX ............37 Fault, handling ............36 Temperature out of range........36 Floor cooling ............19 Temporary setpoint..........13 57 / 58 Siemens RDF302 Basic documentation CE1P3079en Building Technologies Index 07 Dec 2011...