Control outputs configuration
(setting via DIP switches 4/5 and parameters)
(2-position)
Fan
3-/1-
3-/1-speed
control:
speed
Type:
RDG10..
RDG110..
With RDG100, RDG100T and RDG100T/H, the function of the control outputs
(2-position or 3-position) is set via DIP switches 4 and 5 .
The patterns of DIP switches 4 and 5 are as follows:
ON
OFF
1
2
3
4
5
Y1/Y2 =
2-position
Y3/Y4 =
2-position
If 2-position is selected, the factory setting is On/Off. If you want PWM (pulse width
modulation), set parameters P46 and/or P47 to 2 = PWM.
With RDG110.. only control output On/Off is available.
With RDG160T.., the function of the control outputs (DC 0...10 V or 2-position) is set
via parameters P46 and P47.
Control output 1
P46=2
P46=1
Control output 2
P47=2
P47=1
For applications with 3-speed fan, only DC 0...10 V control outputs on Y10, Y20 are
available
Type of fan signal can be selected via P53 or DIP4, see section 4.9.
2-position valve actuator control on applications without fan function – sequence of
settings:
– Set DIP 4 to Off and P53 = 3.
– Disable the fan function via parameter P52 = 0
– Set valve actuators to 2-position via P46 and/or P47 = 1
For details concerning connection of peripheral devices and setting of the DIP
switches, refer to the Mounting Instructions:
– [4] M3181.1 (RDG100, RDG100T)
RDG100.., RDG110.., RDG160T.. Basic Documentation
Functions
Control outputs
On/Off
DC fan
RDG160..
ON
ON
OFF
OFF
1
2
3
4
5
2-position
3-position
DC 0...10V signal
2-position signal
DC 0...10V signal
2-position signal
Mod. PWM
Mod.
(2-pos.)
3-pos.
3-/1-speed
3-/1-speed
RDG10..
RDG10..
( ) *
*
Only possible for 1 actuator
ON
OFF
1
2
3
4
5
3-position
2-position
Y10 terminal
Factory setting
Q1 terminal
Y20 terminal
Factory setting
Q2 terminal
Mod. DC
0...10 V
3-/1-speed,
DC fan
RDG160..
1
2
3
4
5
3-position
3-position
27/81
CE1P3181en
2015-07-29