Advertisement

5.4 E2 Troubleshooting
Digital display output
Description
Communication error between outdoor unit and user interface.
Communication failure between master and slave units
All units stop running.
Error code is displayed on main PCB and user interface.
Possible causes
Communication wires between outdoor unit and user interface not connected properly.
For SCV-900EB, Communication wiring P Q E terminals misconnected. For SCV-750EB, SCV-1400EB SCV-1800EB,
Communication wiring X Y E terminals misconnected
Wiring connection is loosen
Interference from high voltage wires or other sources of electromagnetic radiation.
Communication wire too long.
Damaged main PCB, user interface or electric control box communication terminals block.