5.2 E0/H9 Troubleshooting
Digital display output
Description
For SCV-750EB and SCV-1400EB
E0 indicates that the capability dialing code of the main PCB is inconsistent with the actual model.
1H9 indicates that the driving model of IPM inverter module (compressor A) does not match.
2H9 indicates that the driving model of IPM inverter module (compressor B) does not match.
All units stop running.
Error code is displayed on main PCB and user interface...d user interface.
For SCV-900EB and SCV-1800EB
E0 indicates main PCB EEPROM error.
1H9 indicates IPM inverter module (compressor A) EEPROM error.
2H9 indicates IPM inverter module (compressor B) EEPROM error.
All units stop running.
Error code is displayed on main PCB and user interface...d user interface.
Possible causes
For SCV-750EB and SCV-1400EB
The dialing code of main PCB capability is error.
The address dialing code of the IPM inverter module PCB is error.
Main PCB or IPM inverter module damaged.
For SCV-900EB and SCV-1800EB
Main PCB or IPM inverter module EEPROM is not connected properly.
Main PCB or IPM inverter module damaged.
EEPROM damaged.