5.18 PC Troubleshooting
Digital display output
Description
Water side heat exchanger low pressure protection.
All units stop running.
Error code is displayed on main PCB and user interface.
Possible causes
Low pressure switch not connected properly or has malfunctioned.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange in heating mode.
Insufficient water flow in cooling mode.
Main PCB damaged.
108