5.27 F2 Troubleshooting
Digital display output
Description
Insufficient protection of exhaust superheat.
All units stop running.
Error code is only displayed on main PCB and user interface.
Possible causes
Discharge pipe temperature sensor connected properly or has malfunctioned.
For SCV-750EB and SCV-1400EB, discharge pipe temperature sensor at the top of the compressor falls or is not insulated.
For SCV-900EB and SCV-1800EB, electronic expansion valve coil not connected properly or has malfunctioned.
Damaged main PCB.