Sinclair SCV-750EB Service Manual page 123

Air-cooled modular chiller unit
Hide thumbs Also See for SCV-750EB:
Table of Contents

Advertisement

4.
Check the wired connection between CN36 of filter board and CN2/CN3 of compressor module board, the normal voltage should be 230AC.
Check the wired connection between CN30 of filter board and CN58 of main control board, the normal voltage should be DC12V.
121