Sinclair SCV-750EB Service Manual page 32

Air-cooled modular chiller unit
Hide thumbs Also See for SCV-750EB:
Table of Contents

Advertisement

For SCV-750EB and SCV-1400EB:
Component
Water pump
Inverter compressor 1
Inverter compressor 2
Inverter fan1
Inverter fan 2
Electronic expansion valve
Electronic expansion valve
Electronic expansion valve
Four-way valve
Solenoid valve (defrost)
Solenoid valve (by pass)
Solenoid valve (injection)
Water flow switch
Water flow switch heater
Crank case heater
For SCV-1800EB:
Component
Inverter compressor
DC fan motor
Electronic expansion valve
Four-way valve
30
75kW
Wiring diagram label
PUMP
BP1
BP2
FAN1
FAN2
EXV-A
EXV-B
EXV-C
ST1
SV5
SV6
SV8A/B
Water-SW
CCH
Wiring diagram
label
BP1/2
FAN
EXV
ST1
140kW
Control functions and states
Non-standard component: After the pump is turned on for 2
minutes, detect the water flow switch continuously. The
compressor can be started only after the water flow is
normal.
Control the outlet water temperature. The operating
increased and decreased frequency is 1Hz/s, and is executed
according to the starting platform.
Control According to the exhaust pressure of the outdoor
unit, the initial target windshield is operated for the first
60s, and then correct every 20-60s.
Step from 0 to 480. Controlled according to discharge
temperature superheat.
Step 480P
Step from 0 to 480. Controlled according to temperature
difference between economizer plate heat exchanger inlet
and outlet.
Open
Closed
Open for 600s, then closed.
Open
After water pump (field supplied) is turned on for 2min, if
water flow switch is open, water pump stops and water flow
error code appears. The compressor can be started after the
water flow is normal.
Controlled according to ambient temperature, water inlet
temperature and water outlet temperature.
Controlled according to ambient temperature and discharge
temperature.
180kW
Control functions and states
Compressor startup program selected according to ambient
1
temperature
.
Fan run at maximum speed
Position (steps) from 0 (fully closed) to 480 (fully open),
controlled according to outdoor ambient temperature,
discharge temperature, suction superheat, compressor speed
and refrigerant system pressure.
Off