Procedure
The inverter compressor module
The screws connecting the heat sink to the
inverter module are loose
Fan motor wiring connection is wrong
Replace outdoor main PCB
Notes:
1.
Refer to Part 4, 1 "Electric Control Box Layout".
PL/C7
1
heat sink
is blocked or dirty
No
1
No
No
Yes
Clean or replace the heat sink
Tighten the screws and make sure the heat
Yes
sink is well-connected
Yes
Check the fan motor wiring connection
115