5.23 F0 Troubleshooting
Digital display output
Description
1F0 indicates a communication error between the main control chip and the compressor A inverter driver chip.
2F0 indicates a communication error between the main control chip and the compressor B inverter driver chip.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Main control chip and inverter driver chip cannot communication for 2 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes
Incorrect compressor inverter module address setting.
Loosened communication wiring from the main PCB to
the inverter module.
Procedure,
For SCV-750EB and SCV-1400EB
Compressor inverter module address setting
Communication wire from outdoor main
PCB CN26 to inverter module CN8/CN9 is
LED3 on inverter module are off when
Replace the outdoor main PCB, is the
Replace the inverter module
118
F0 error
is incorrect
No
loosened
2
No
3
power on
No
malfunction solved?
No
Bridge rectifier damaged.
Main PCB damaged.
Compressor inverter module damaged.
Reset the compressor inverter
Yes
module address via dial switch
S7 on inverter module
Yes
Reconnect the communication
wire
Yes
Check the power supply circuit
Yes
Normal
1
4