Procedure
If possible, switch the compressors and start up again. If the problem persists, replace the two compressors.
6.15 L60: Fan motor phase loss protection
Description
Compressor has phase loss protection.
After the fault, the compressor stops running, and if the fault disappears after one minute, the compressor starts again.
Trigger/resume condition
Trigger condition: The compressor wire is not connected or has poor contact.
Resume condition: Check the wiring of the compressor. After wiring again, the phase loss protection fault is eliminated.
Reset method: Automatic recovery after reaching the fault exit condition.
Possible causes
The compressor wire is not in good contact or the terminal screws are not tightened.
Module board is abnormal.
Procedure
Check the UVW output connection wire of the compressor drive board, and check the UVW wiring of the compressor;
If possible, switch the compressor wire to confirm whether the drive board is normal, otherwise replace the drive board.
6.16 L61: Short circuit to ground protection
Description
Compressor has short circuit to ground protection.
After the fault, the compressor stops running, and if the fault disappears after one minute, the compressor starts again.
Trigger/resume condition
Trigger condition: Compressor has short circuit to ground protection.
Resume condition: Check whether the compressor casing is damaged, resulting in poor insulation.
Reset method: Automatic recovery after reaching the fault exit condition.
Possible causes
The compressor casing is in poor insulation.
Procedure
Disconnect the compressor wire, measure the compressor UVW resistance to ground, confirm and replace the compressor.
6.17 L65: IPM short circuit protection
Description
The IPM corresponding to the compressor has short circuit protection.
After the fault, the compressor stops running, and if the fault disappears after one minute, the compressor starts again.
Trigger/resume condition
Trigger condition: The IPM corresponding to the compressor has short circuit protection.
Resume condition: Replace the drive board.
Reset method: Automatic recovery after reaching the fault exit condition.
Possible causes
There is a problem with drive board.
Procedure
Check whether the IPM virtual welding and the PWM related transmission circuit of the MCU are connected to the welding.
If so, change the replace the drive board.
6.18 L6b: Open circuit of U-phase lower tube
Description
Open circuit of U-phase lower tube.
After the fault, the compressor stops running, and if the fault disappears after one minute, the compressor starts again.
149