Procedure
Some power wires or communication wires
of fan module are not connected properly
The fan motor is blocked or has failed
The power supply is abnormal
Voltage between P and N on fan module is
Replacing the fan module resolves the error
Replace main PCB
Notes:
1.
Refer to Part 4, 3 "Wiring diagram" and PCB components to make sure wire connection is firm.
2.
The normal voltage between P and N on the fan module is 650V DC. Refer to Part 4, 1 "Outdoor Unit Electric Control Box Layout" and to Part 4, 2.4 "Fan
module board".
PU/FF
No
No
No
No
abnormal
2
No
No
Ensure power and communication wires are
Yes
1
Yes
Remove obstruction or replace the fan motor
Yes
Check the power supply equipment
Yes
connected properly
Replace AC filter board
117