5.22 PU/FF Troubleshooting
Digital display output
Description
1PU/FF indicates fan A module protection.
2PU/FF indicates fan B module protection.
FF indicates PU protection has displayed 10 times. When a FF occurred, a manual system restart is required before the
system can resume operation.
All units stop running.
Error code is only displayed on the main PCB and user interface.
Possible causes
Switch SW1 incorrectly set.
Power or communication wires not connected properly.
Fan motor blocked or has failed.
Power supply abnormal.
AC filter board damaged.
Fan module damaged.
Inverter module PCB damaged.