Sinclair SCV-750EB Service Manual page 60

Air-cooled modular chiller unit
Hide thumbs Also See for SCV-750EB:
Table of Contents

Advertisement

Label
2.7 Slave PCB Board
For SCV-750EB and SCV-1400EB only:
Label
Code
1
CN140
2
CN115
3
CN125
4
CN123
5
CN121
6
CN119
7
CN108
8
CN110
9
CN138
10
CN114
WATER-SWITCH
11
CN105
12
CN101
13
CN103
14
CN300
15
CN109
58
Code
Port
1
CN26
2
CN27
Port
POWER
Slave PCB board strong power supply
W-HEAT
Water pipe electric heating belt
Three-way valve for making hot water (used for customized hot
3-way valve
water models)
PUMP
Port for water pump contactor control (for market installation)
COMP-STATE
Compressor Status Indication
HEAT1
Pipe auxiliary motor heating belt
PUMP-V
Frequency conversion pump 0-10V control signal
W.P-SW
Water pressure difference switch
TEMP-SW
Target water temperature switch
COOl/HEAT
Remote mode control
ON/OFF
Remote switch control
Water flow switch
Taf1
Water tank anti-freeze sensor
TW
Total water sensor
T5
Water tank sensor
DEBUG
Main control program burn port (WizPro200RS programmer)
MS
Communication port of slave PCB board and main PCB board
Explanation
For connecting compressor module board
For connecting compressor module board
Explanation
Voltage
/
/
Voltage
220-240V
220-240V
220-240V
220-240V
/
/
DC 0-10V
DC12V
DC12V
DC12V
DC12V
DC12V
DC3.3V
DC3.3V
DC3.3V
DC3.3V
DC12V/DC3.3V

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scv-900ebScv-1400ebScv-1800eb