Deployment
Accessing the web server via Ethernet > Web server

4.6 Accessing the web server via Ethernet

Access via Ethernet (EoE)

4.6.1 Web server

Activate / deactivate web
server
78
On delivery the EtherCAT coupler has no IP address. To be able to access the EtherCAT
coupler via EoE, you have to assign data to this IP address. The following options in the
SPEED7 EtherCAT Manager are available:
Configuration - slave station - Ethernet (EoE)
n
Port Mode:
Switch Port (is not supported)
IP Port
n
Overwrite IP Settings:
IP Address
Subnet Mask
Default Gateway
DNS Server (is not supported)
DNS Name (is not supported)
The activation is carried out via the Command object 0x2000 (Default: deactivated).
Ä 'Command' page 93
Procedure
n
Use Parameter (object 0x2000:02) to determine whether the web server is enable
("1") or disable ("0"),
n
use Execute Command (object 0x2000:01) to issue the command 0x00008001 (Set
web server state),
n
Status (object 0x2000: 03) indicates whether the command was executed success-
fully or incorrectly.
1: Command executed
2: Command not executed
3: Command unknown
4: Command not executable in this state
The setting is saved remanently.