System SLIO

3.4 Technical data

Order no.
Type
Module ID
Technical data power supply
Power supply (rated value)
Power supply (permitted range)
Reverse polarity protection
Current consumption (no-load operation)
Current consumption (rated value)
Inrush current
I²t
Max. current drain at backplane bus
Max. current drain load supply
Power loss
Status information, alarms, diagnostics
Status display
Interrupts
Process alarm
Diagnostic interrupt
Diagnostic functions
Diagnostics information read-out
Supply voltage display
Service Indicator
Group error display
Channel error display
Hardware configuration
Racks, max.
Modules per rack, max.
Number of digital modules, max.
Number of analog modules, max.
Communication
Fieldbus
Type of interface
Connector
Topology
Electrically isolated
HB300 | IM | 053-1EC01 | en | 22-30
053-1EC01
IM 053EC
-
DC 24 V
DC 20.4...28.8 V
ü
95 mA
0.95 A
3.9 A
0.14 A²s
3 A
10 A
3 W
yes
yes, parameterizable
yes, parameterizable
yes, parameterizable
yes, parameterizable
possible
green LED
yellow LED
red SF LED
none
1
64
64
64
EtherCAT
Ethernet 100 MBit
2 x RJ45
Line
ü