Replace EtherCAT slave 053-1EC00 with 053-1EC01

Settings
HB300 | IM | 053-1EC01 | en | 22-30
It is not possible to copy modules and their properties / configuration from
EtherCAT Slave 053-1EC00 to EtherCAT Slave 053-1EC01 since the
EtherCAT slaves come from different ESI files.
When replacing an EtherCAT slave 053-1EC00 by 053-1EC01 an adaptation of your
project is required. When replacing the EtherCAT slaves, make sure that all settings and
parameters of the 053-1EC00 EtherCAT slave that deviate from the standard setting are
transferred to the EtherCAT slave 053-1EC01. Therefore, these settings should be saved
appropriately before the replacement. Precondition for replacing the EtherCAT slave
053-1EC00 by 053-1EC01 is that the ESI file for the EtherCAT slave 053-1EC01 is
installed in the configuration tool. The replacement takes place in the configuration by
deleting the EtherCAT slave 053-1EC00 and adding the EtherCAT slave 053-1EC01. In
the following all settings are listed, which should be noted.
n
EtherCAT station address
If the station address does not match that of the EtherCAT Slave 053-1EC00,
there is a topology error. The EtherCAT slave is not controlled.
n
Position of the EtherCAT slave on the bus
If the position of the EtherCAT slave on the bus does not match the position of the
EtherCAT slave 053-1EC00, there is a topology error. The EtherCAT slave is not
controlled.
n
Slot assignment of the modules
As long as the total IO size of the EtherCAT slave matches the configured size of
the master, the EtherCAT slave can switch to Operational (Op). If the slot assign-
ment is changed, the wrong process data of the modules is transmitted
n
Download the slot configuration
If this option was activated for the EtherCAT slave 053-1EC00, then this option
should also be activated for the EtherCAT slave 053-1EC01. Please pay attention
to an identical slot assignment. If the slot configuration fits between master and
053-1EC01 but deviates from the slot configuration of EtherCAT slave
053-1EC00, this deviation is not recognized!
n
PDO mapping of the modules
For modules with variable IO size, for this modules the PDO mapping of the
053-1EC01 should be set exactly the same as for the 053-1EC00. Otherwise, the
slave does not change to Safe-Op or Op.
n
CoE init commands
The CoE init commands at the 053-1EC01 should be made the same as with the
053-1EC00. If there are deviations, the EtherCAT slave can switch to Op, but
there is a possibility that the EtherCAT slave or its modules will not behave as
expected.
Replace EtherCAT slave 053-1EC00 with 053-1EC01