Setting Procedure; Set Value Writing In The Exclusive Data Area (Using Request Flag 1); (Using Request Flag 2) - Unipulse F372A Operation Manual

Cc-link i/f
Hide thumbs Also See for F372A:
Table of Contents

Advertisement

8.

Setting Procedure

■Set value writing in the exclusive data area (using request flag 1)

Request flag 1 is used when Setting value is written in. The Setting value is written in at Request
flag ON edge when Request flag 1, 2 and Request flag response 1, 2 are OFF.
RWw0000 to RWw0009 when 4 stations occupied and RWw0000 to RWw0003 when 2 stations
occupied become Exclusive data area. It is stored in selected WORK by WORK No.
① Input Work No. to write to the Work No. area.
② Set a value in all the corresponding set value area out of HH Limit, HI Limit, LO Limit and
LL Limit.(When 4 stations occupied)
③ Make request flag 1 of the remote output 0→1.
④ After confirming response flag 1 of the remote input 0→1, make request flag 1 of the remote
output from 1→0.
ex.) When 4 stations occupied
Request flag 1
Request flag 1 response
Exclusive data area
WORK No.
(RWw000F)
■Set value writing and operation command in the general-purpose
data area (using request flag 2)
Turn OFF R/W when writing in Setting value and executing operation command. It is operated at
ON edge of Request flag 2 when Request flag 1, 2 and Request flag 1, 2 response are OFF.
RWw000C to RWw000D when 4 stations occupied and RWw0004 to RWw0005 when 2 stations
occupied become General purpose data area.
RWw000E when 4 stations occupied and RWw0006 when 2 stations occupied become Command
No. area.
RWw000F when 4 stations occupied and RWw0007 when 2 stations occupied become WORK No.
area.
It is stored in selected WORK by WORK No., when writing in setting value.
① Input Work No. to write to the Work No. area.
② Input the command of the set value to be written in the Command area in the general-purpose
data area.
③ Input the value to be written or to give an operation command to the data in the general
purpose area.
④ Set R/W of the remote output to 0.
⑤ Make request flag 2 of the remote output 0→1.
⑥ After confirming response flag 2 of the remote output 0→1, make request flag 2 of
the remote output 1→0.
⑦ Responses are stored in R/W (response) of the remote input and general-purpose data area (response).
Confirm the contents of the general-purpose data area (response).
(RY0000)
(RX0000)
(RWw0000)
(RWw0009)
(The Upper row of signal level is ON. The Lower row of signal level is OFF.)
8.Setting Procedure
Range: 0 to 15
Range: 0 to 15
17