High/low user defined alert
7.2.14
Low user defined alert
Category
Cause
The user defined variable is below the defined limit.
Recommended actions
Related information
High/low user defined alert
7.2.15
Linearized variable out of range
Category
Cause
The level measurement is outside the configured range for volume or scaled variable, or
both.
Accuracy of volume/scaled variable measurement may be degraded.
Recommended actions
Related information
Volume
Scaled variable
7.2.16
Dielectric constant estimation degraded
Category
Rosemount 3408 Level Transmitter
4. If not needed, disable this alert.
Maintenance Required
1. Bring the system to a safe state.
2. Verify that the process variable is within specified limits.
3. Reconfirm the user defined alarm limit.
4. If not needed, disable this alert.
Maintenance Required
1. If volume strapping table is used, make sure level values within operating range
are included.
2. If scaled variable table is used, make sure input variable values within operating
range are included.
Maintenance Required
Service and troubleshooting
September 2022
67