Configuration error
Category
Cause
The device has detected a configuration error. Reasons may be multiple.
Recommended actions
Volume configuration error
Cause
The volume cannot be calculated correctly with the current configuration.
Recommended actions
Related information
Volume
Geometry
Restore to default settings
Configure transmitter using guided setup
Scaled variable configuration error
Cause
The Scaled Variable configuration is incorrect.
Recommended actions
Rosemount 3408 Level Transmitter
Failure
1. Click the Details button for more information.
2. Correct the parameter causing the error.
1. If strapping table is used, check that level-volume values are entered in
increasing order.
2. If strapping table is used, check that number of strapping points to use is
correct.
3. If tank dimensions are used for volume, check that geometry shape and size
measures are correct.
4. If condition persists, restore default settings and reconfigure the device.
1. Check that the value pairs in the scaled variable table are entered in increasing
order.
Service and troubleshooting
September 2022
59