Emerson Rosemount 3408 Reference Manual page 65

Level transmitter, non-contacting radar
Hide thumbs Also See for Rosemount 3408:
Table of Contents

Advertisement

Reference Manual
00809-0100-4418
Restore to default settings
Configure transmitter using guided setup
Start code configuration error
Cause
The start code to enable options in the device is invalid.
Note
Start codes are unique for individual devices and cannot be copied from one device to
another.
Recommended actions
7.2.9
Safety mode not activated
Category
Cause
Safety Mode is disabled and device is in alarm mode.
This device is configured for use in Safety Instrumented Systems (SIS) which requires
Safety Mode to be enabled.
Recommended actions
Related information
Rosemount 3408 Safety Manual
7.2.10
Simulation/test active
Category
Cause
The device is in simulation or test mode and is not reporting actual information.
Recommended actions
Rosemount 3408 Level Transmitter
1. Enter a valid start code for this device using the Upgrade function.
2. If condition persists, contact your local Emerson representative to get a valid
start code.
Function Check
1. Change Safety Mode to Enabled for use in SIS application.
2. Change Operational Mode to Control/Monitoring if device is not intended to be
used as safety device.
Function Check
1. If this behavior is not desired, stop simulation or test mode.
2. If the condition persists, restart the device.
Service and troubleshooting
September 2022
65

Advertisement

Table of Contents
loading

Table of Contents