10.2 List of messages displayed on MENU 1/3-ALM/FLT screen

Alarm type
DMV
Manipulated output change rate
MVL
Manipulated output low limit alarm
(-25.00 to 125.00%)
MVH
Manipulated output high limit alarm
(-25.00 to 125.00%)
DVL
Deviation low limit alarm (0.00 to 100.00%)
DVH
Deviation high limit alarm (0.00 to 100.00%)
DPL
Process variable change rate low limit alarm
(0.00 to 100.00%)
DPH
Process variable change rate high limit
alarm (0.00 to 100.00%)
PVL
Process variable low limit alarm (settable
range depends on industrial value)
PVH
Process variable high limit alarm (settable
range depends on industrial value)
SVL
Setpoint low limit alarm (settable range
depends on industrial value)
SVH
Setpoint high limit alarm (settable range
depends on industrial value)
Fault type
AI CHECK
AI check (ON/OFF)
DAI CHECK
Direct input AI check (ON/OFF)
OPTION AI
Direct input board down
MV R-BACK
MV read-back error
Warning type
FLASH WAR
Flash ROM faulty
OPT COM ER
OPTO 22 transmission faulty
WAF STOP
Wafer stop
CNCT ERROR
Wafer connection faulty
ISA STOP
Soft PLC stop
Front FLT (fault) lamp status
Blink
Lit
INP-TN1PDA3-E
Alarm meaning (settable range)
Fault meaning
Warning meaning
Warning being produced
Fault being produced
Judging criterion
According to setting
According to setting
According to setting
According to setting
According to setting
According to setting
According to setting
According to setting
According to setting
According to setting
According to setting
Input range beyond -11.50 to 111.50%
Input range beyond -5.00 to 105.00%
Direct input board abnormal
Read-back error beyond ± 10.00% or
more or MV output open
Flash ROM write, delete failed
OPTO 22 transmission faulty
Wafer computation stopped
Wafer connected abnormally
Soft PLC computation stopped