Gree FP-22LM/D-K Owner's Manual

Gree FP-22LM/D-K Owner's Manual

Vertical exposed fan coil unit
Hide thumbs Also See for FP-22LM/D-K:

Advertisement

Change for life
Owner's Manual
Original Instructions
Commercial Air Conditioners
Vertical Exposed Fan Coil Unit
Models:
FP-22LM/D-K
FP-34LM/D-K
FP-51LM/D-K
FP-68LM/D-K
FP-85LM/D-K
FP-102LM/D-K
FP-119LM/D-K
FP-136LM/D-K
FP-170LM/D-K
FP-204LM/D-K

Advertisement

Table of Contents
loading

Summary of Contents for Gree FP-22LM/D-K

  • Page 1 Change for life Owner's Manual Original Instructions Commercial Air Conditioners Vertical Exposed Fan Coil Unit Models: FP-22LM/D-K FP-34LM/D-K FP-51LM/D-K FP-68LM/D-K FP-85LM/D-K FP-102LM/D-K FP-119LM/D-K FP-136LM/D-K FP-170LM/D-K FP-204LM/D-K...
  • Page 2 To users Thank you for selecting Gree’s product. Please read this instruction manual carefully before installing and using the product, so as to master and correctly use the product. In order to guide you to correctly install and use our product and achieve expected operating effect, we hereby instruct as below: (1) This equipment should be installed, operated or maintained by the qualified servicemen who have had specific training.
  • Page 3: Table Of Contents

    Contents Safety notices (please be sure to abide ) ............... 1 1 Product introduction ..................... 5 1.1 Working principle ......................5 1.2 Main parts ......................... 5 1.3 Working conditions ......................5 2 Unit installation ...................... 5 2.1 Installation environment ....................5 2.2 Precautions for installation ....................
  • Page 4: Safety Notices (Please Be Sure To Abide )

    Vertical Exposed Fan Coil Unit Safety notices (please be sure to abide ) WARNING: If not abide strictly, it may cause severe damage to the unit or the people. NOTE: If not abide strictly, it may cause slight or medium damage to the unit or the people. This sign indicates that the operation must be prohibited.
  • Page 5 Please contact insulated so as to prevent from GREE after-sales center and dewing in summer. repair should be done by the qualified servicemen. Never splice the power cord or Don’t insert your hands or stick...
  • Page 6 The connection line should once, and then contact GREE not suffer external forces. For after-sales servicemen. If the unit equipped with the...
  • Page 7 Vertical Exposed Fan Coil Unit This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial or household use by lay persons. Installing the unit in the following places may cause malfunction. If it is unavoidable,please consult the local dealer: (1) The place with strong heat sources,vapors, flammable or explosive gas,or volatile objects spread in the air.
  • Page 8: Product Introduction

    Vertical Exposed Fan Coil Unit 1 Product introduction 1.1 Working principle The cold (hot) water entering the heat exchanger will do heat exchanging with air passing through the surface of the heat exchanger to condition the air temperature and humidity. There is no (cold) hot source for this product itself.
  • Page 9: Precautions For Installation

    Vertical Exposed Fan Coil Unit 2.2 Precautions for installation Drill four holes on the wall for suspending the unit in accordance with the the table below. Suspension hole Suspension hole Unit: mm Model α β FP-22LM/D-K FP-34LM/D-K FP-51LM/D-K FP-68LM/D-K FP-85LM/D-K FP-102LM/D-K FP-119LM/D-K 1010 FP-136LM/D-K...
  • Page 10 Vertical Exposed Fan Coil Unit Open the cover. Loosen three screws and lift the decorated panels (on left or right side) 1cm above and remove them in a horizontal way. Lift the decorated panels (on left or right side) 1cm above Open the cover Loosen screws After...
  • Page 11: Outline Dimensions

    Vertical Exposed Fan Coil Unit 2.3 Outline dimensions Outlet pipe size Rc3/4 Inlet pipe size Rc3/4 Drain pipe size φ22 Unit: mm Model FP-22LM/D-K FP-34LM/D-K FP-51LM/D-K 1050 FP-68LM/D-K 1050 FP-85LM/D-K 1050 FP-102LM/D-K 1350 1023 FP-119LM/D-K 1350 1023 FP-136LM/D-K 1350 1023...
  • Page 12: Installation Of The Drain Hose

    Vertical Exposed Fan Coil Unit (3) Metallic hoses similar to the picture below are recommended for inlet and outlet pipes. (4) Pipe connectors and electric valve threads should be bounded with teflon tapes (5) Fixing all water pipes tightly, start the water pump and check if there is leakage. Use the exhaust valve to release all the gases inside pipes.
  • Page 13: Installation Of The Water Valve

    Vertical Exposed Fan Coil Unit 2.6.2 Installation steps of the drain pipe (When drain hose is connected) Tilt the drain hose Clamp Not to be lifted No foldings Not to be soaked Sponge Drain hose in water Sponge Air outlet Clamp Watering can <4mm...
  • Page 14 Vertical Exposed Fan Coil Unit (5) When the water pipe and water valve have been installed, connect the connection line of the valve to the wiring board of the unit. (6) Check the wiring carefully and then start the water pump and unit to see if they work normally. 2.7.2 Requirements on installation (1) The water valve should be installed as the following statement;...
  • Page 15: Electric Wiring

    Vertical Exposed Fan Coil Unit 2.8 Electric wiring 2.8.1 Precautions for electric wiring (1) All electric wiring should be performed by the qualified technical in accordance with local standards, regulations and this manual. (2) The specialized electric circuit with rated voltage should be used for the power supply. (3) Do not pull the power supply lines by force.
  • Page 16: Thermostat Guide

    Vertical Exposed Fan Coil Unit 3 Thermostat guide 3.1 Thermostat panel and keys Cooling mode Temperature or failure codes Air supplying mode Child lock Heating mode ON/OFF Fan speed MODE Timer SPEED Drying function Sleep function DOWN 3.2 Technical parameters Item Description Supply voltage...
  • Page 17: Thermostat Operations

    Vertical Exposed Fan Coil Unit 3.3 Thermostat operations The thermostat backlight will be off after 20 continuous seconds without a key press on the panel or the remote controller. Then, any key press on the panel will enable the backlight (that will flash once if the user operates the remote controller) indicating that the user can begin to use the thermostat.
  • Page 18 Vertical Exposed Fan Coil Unit 3.3.4 Temperature setting (1) During the operation of the unit, press (UP) or (DOWN) to raise or lower the temperatures. (2) When the temperature unit is Celsius, one press of the UP key or the DOWN key causes a 0.5°C increase or decrease within 16°C~30°C.
  • Page 19 Vertical Exposed Fan Coil Unit 3.3.6 Child lock After a start or stop of the unit, press keeping of both (UP) or (DOWN) enables or disables the child lock that will recover after the power failure. As shown in the Figure 5, the symbol that appears will be activated to flash for 3 seconds by a press of any other keys, reminding the user of the child lock functioning.
  • Page 20 Vertical Exposed Fan Coil Unit Parameter list: Name Description Power failure memory ON: enable (by default); OFF: disable Energy saving function ON: enable; OFF: disable (by default) Drying function ON: enable; OFF: disable (by default) Temperature unit setting F: Fahrenheit; C: Celsius (by default) 00: the fan works as to the set speed;...
  • Page 21 Vertical Exposed Fan Coil Unit (2) Energy saving function The unit is allowed to cool or heat in the energy saving mode (08, 09 in the list). Energy will be saved when the air conditioner operates within a small range by limiting the cooling and heating temperatures. y The sleep mode is also available upon the energy saving mode.
  • Page 22 Vertical Exposed Fan Coil Unit (4) Temperature unit setting Celsius (°C) or Fahrenheit (°F) is available. As shown in the Figure 10, on the parameter setting page, press (MODE) to switch the option number to 04. (UP) or (DOWN) is provided to allow a switch between Celsius (°C) and Fahrenheit (°F).
  • Page 23 Vertical Exposed Fan Coil Unit (7) Temperature variation range With the narrow range, the temperature features a small amount of variation for great comfort, but the fan and water valve will operate more frequently causing loss of service life. Whereas, the wide range does good to duration of the fan and water valve with a large amount of temperature variation and low frequency operation.
  • Page 24 Vertical Exposed Fan Coil Unit (9) Heating temperature set in the energy saving mode It is available when energy saving function is enabled. The heating temperature is limited between 16°C and 30°C (61°F~86°F). As shown in the Figure 15, on the parameter setting page, press (MODE) to switch the option number to 09.
  • Page 25: Ambient Temperature Sensor Failure

    Vertical Exposed Fan Coil Unit (11) Factory data reset All parameters (3.3.8) can be reset to factory defaults. As shown in the Figure 17, on the parameter setting page, press (MODE) to switch the option number to 11. (UP) or (DOWN) is provided to allow a switch between ON and OFF.
  • Page 26: Commissioning And Maintenance

    Vertical Exposed Fan Coil Unit 4 Commissioning and maintenance 4.1 Inspection after installation Item Possible consequence Inspection The unit may fall down, vibrate or Is the main unit installed securely? generate noise. Is the leak test performed? The unit fails to work normally. It may generate condensate and water Is the unit insulted properly? drops.
  • Page 27: Troubleshooting

    Vertical Exposed Fan Coil Unit 5 Troubleshooting Symptoms Possible causes Corrective measures Repower the unit when power supply is There is no power supply. available. The unit does The power plug is loosened. Tighten the power plug. not run. The motor is burnt out. Replace the motor and check for the wiring The volute or blade is deformed, or Replace the volute or the blade.
  • Page 28 GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070 Tel: (+86-756) 8522218 Fax: (+86-756) 8669426 E-mail: global@cn.gree.com www.gree.com...