Gree GWHD(48S)NM3CO Service Manual

Gree GWHD(48S)NM3CO Service Manual

Super free match series
Hide thumbs Also See for GWHD(48S)NM3CO:
Table of Contents

Advertisement

CENTRAL AIR CONDITIONERS
SUPER FREE MATCH SERIES

SERVICE MANUAL

T1/R410A/50Hz
( GC201405 - )

Advertisement

Table of Contents
loading

Summary of Contents for Gree GWHD(48S)NM3CO

  • Page 1: Service Manual

    CENTRAL AIR CONDITIONERS SUPER FREE MATCH SERIES SERVICE MANUAL T1/R410A/50Hz ( GC201405 - )
  • Page 2: Table Of Contents

    Contents PRODUCT ........................2   MODELS LIST........................2     Outdoor Unit ..........................2     BU Module..........................2     Indoor Unit..........................2     NOMENCLATURE .......................5     Nomenclature of Outdoor Unit ....................5     Nomenclature of BU Module....................5     Nomenclature of Indoor Unit....................5  ...
  • Page 3 Super Free Match Service Manual FLOW CHART OF INSTALLATION.................65     OUTDOOR UNIT INSTALLATION ..................66     Precautions for R410A......................66     Precaution for Installation....................66     Precaution for Operation Test ....................66     Names of Main Parts......................66     Parts and Components of Unit .....................67  ...
  • Page 4 Super Free Match Service Manual Material Quality Requirements for Condensate Pipe ............113     Key Points for Condensate Pipe Installation..............113     Installation of Protective Layer on Connection Pipe ............117     MAINTENANCE ....................119   Testing Board Introduction ....................119  ...
  • Page 5 Super Free Match Service Manual PRODUCT PRODUCT...
  • Page 6: Product

    Super Free Match Service Manual PRODUCT 1 MODELS LIST 1.1 Outdoor Unit Capacity Capacity Power supply Refriger Model Product code Cooling Heating Appearance Ph, V, Hz (kW) (kW) GWHD(48S)NM CN860W0110 14.0 16.0 R410A 3,380~415,50 GWHD(56S)NM CN860W0120 16.0 18.0 1.2 BU Module Number of connectable Power supply Model...
  • Page 7 Super Free Match Service Manual U-cool Capacity Power supply Refrige Model Product code Appearance Cooling Heating rant Ph, V, Hz (kW) (kW) CB204N02600 GWH(07)UA-K3DNA1B/I CB204N02700 GWH(09)UA-K3DNA1B/I R410A 1,220~240,50 CB204N02800 GWH(12)UB-K3DNA1B/I CB204N02900 GWH(18)UC-K3DNA1B/I Cozy Capacity Power supply Refrige Model Product code Cooling Heating Appearance...
  • Page 8 Super Free Match Service Manual 1.3.3 Cassette type Capacity Power supply Refrige Model Product code Appearance Cooling Heating rant Ph, V, Hz (kW) (kW) CN510N0040 GKH(12)BA-K3DNA2A/I CN510N0050 GKH(18)BA-K3DNA2A/I CN510N0010 3.85 R410A 1,220~240,50 GKH(12)BA-K3DNA1A/I CN510N0020 GKH(18)BA-K3DNA1A/I CN510N0030 GKH(24)BA-K3DNA1A/I 1.3.4 Floor ceiling type Capacity Power supply Refrige...
  • Page 9: Nomenclature

    □ □ (□) □ □ □ □ □ □ □ Description Options GREE W: Wall mounted type F:Duct type Product Type K:Cassette type E:Console T:Floor ceiling type Cooling Function C: Cooling Only H: Heat pump Cooling Capacity 12 represents 12000Btu/h 1kW=3.412KBtu...
  • Page 10: Function

    Super Free Match Service Manual 3 FUNCTION Wall Cassette Floor Console Function Duct type mounted type ceiling type type Fan operation Mode ● ● ● ● ● Auto Swing Controller ● ● ● ● Timer Selector ● ● ● ● ●...
  • Page 11: Product Data

    Super Free Match Service Manual 4 PRODUCT DATA 4.1 Product Data of Outdoor Unit Model Heat pump GWHD(48S)NM3CO GWHD(56S)NM3CO Cooling capacity 14.0 16.0 Heating capacity 16.0 18.0 Cooling 4.40 Nominal input Heating 4.25 EER/COP 2.9/3.2 2.8/3.5 Minimum NO. of connectable indoor units Maximum NO.
  • Page 12: Product Data Of Indoor Unit

    Super Free Match Service Manual Notes: a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27℃ DB, 19℃WB. Outdoor Temperature is 35℃DB. The rated heating capacity data is measured under the following work condition: Indoor Temperature is 20℃DB. Outdoor Temperature is 7℃DB, 6℃WB. b.
  • Page 13 Super Free Match Service Manual Model GWH(18)TC-K3DNA1E/I GWH(28)TD-K3DNA1C/I Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 Motor power input 0.045 m3/h 1200 Air flow volume Sound pressure level dB(A) 49/44/41/39/36/33/30 52/50/48/45/42/39/35 (SH/H/MH/M/ML/L/SL) Output 0.025 0.07 Fan motor Running current 0.24 inch 5/8″(Φ15.9mm) 5/8″(Φ15.9mm)
  • Page 14 Super Free Match Service Manual U-cool GWH(07)UA-K GWH(09)UA-K GWH(12)UB-K GWH(18)UC-K Model 3DNA1B/I 3DNA1B/I 3DNA1B/I 3DNA1B/I Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.03 0.03 0.04 0.06 m3/h Air flow volume Sound pressure level 37/35/32/30/28/ 38/35/32/30/28/ 39/37/34/31/29/ 44/40/37/35/33/...
  • Page 15 Super Free Match Service Manual Cozy GWH(07)MA-K GWH(09)MA-K GWH(12)MB-K GWH(18)MC-K Model 3DNA3E/I 3DNA3E/I 3DNA3E/I 3DNA3E/I Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.03 0.03 0.04 0.045 Air flow volume Sound pressure level dB(A) 36/34/31/28/- 37/34/31/28/- 38/34/32/30/- 46/43/40/36/-...
  • Page 16 Super Free Match Service Manual Change GWH(07)KF-K GWH(09)KF-K GWH(12)KF-K GWH(18)KG-K Model 3DNA6E/I 3DNA6E/I 3DNA6E/I 3DNA6E/I Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.03 0.03 0.03 0.06 Air flow volume Sound pressure level dB(A) 40/38/30/24/- 41/38/30/24/- 42/39/31/25/- 45/40/37/32/-...
  • Page 17 Super Free Match Service Manual Viola Model GWH(07)RA-K3DNA3E/I GWH(09)RA-K3DNA3E/I Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 Motor power input 0.03 0.03 Air flow volume Sound pressure level (SH/H/M/L) dB(A) 40/37/35/32/- 40/37/35/32/- Output 0.01 0.01 Fan motor Running current 0.14 0.14 inch 3/8″(Φ9.52mm)
  • Page 18 Super Free Match Service Manual GWH(12)RB-K3DN GWH(18)RC-K3DN GWH(24)RC-K3DN Model A3E/I A3E/I A1A/I Cooling 6.45 Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.05 0.06 0.065 1000 Air flow volume Sound pressure level dB(A) 42/39/36/33/- 45/42/37/33/- 48/46/44/42/- (SH/H/M/L) Output 0.02 0.02...
  • Page 19 Super Free Match Service Manual 4.2.2 Duct type GFH(09)EA-K3D GFH(12)EA-K3D GFH(18)EA-K3D Model Heat pump NA1A/I NA1A/I NA1A/I Cooling 2.50 3.50 5.00 Capacity Heating 2.80 3.85 5.50 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.065 0.075 0.08 m3/h Air flow volume Sound pressure level (H/L) dB(A) 37/31...
  • Page 20 Super Free Match Service Manual Model Heat pump GFH(21)EA-K3DNA1A/I GFH(24)EA-K3DNA1A/I Cooling 6.00 7.10 Capacity Heating 6.60 8.00 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 Motor power input 0.11 0.11 m3/h 1000 1000 Air flow volume 588.5 588.5 Sound pressure level dB(A) 42/34 42/34 Output 0.061...
  • Page 21 Super Free Match Service Manual 4.2.3 Cassette Model Heat pump GKH(12)BA-K3DNA2A/I GKH(18)BA-K3DNA2A/I Cooling 3.50 4.50 Capacity Heating 4.00 5.00 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 Motor power input 0.05 0.05 m3/h Air flow volume Sound pressure level(H/L) dB(A) 46/44/42 46/44/42 Output 0.011 0.011 Fan motor...
  • Page 22 Super Free Match Service Manual GKH(12)BA-K3 GKH(18)BA-K3 GKH(24)BA-K3 Model Heat pump DNA1A/I DNA1A/I DNA1A/I Cooling 3.50 5.00 7.10 Capacity Heating 3.85 5.50 8.00 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.07 0.07 0.10 m3/h 1180 Air flow volume Sound pressure level dB(A) 37/35/33...
  • Page 23 Super Free Match Service Manual 4.2.4 Floor ceiling type GTH(09)BA-K3 GTH(12)BA-K3 GTH(18)BA-K3 GTH(24)BA-K3 Model Heat pump DNA1A/I DNA1A/I DNA1A/I DNA1A/I Cooling 2.50 3.50 5.00 7.10 Capacity Heating 2.80 3.85 5.50 8.00 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.055 0.055 0.11...
  • Page 24 Super Free Match Service Manual 4.2.5 Console type GEH(09)AA-K3DNA1 GEH(12)AA-K3DNA1 GEH(18)AA-K3DNA1 Model Heat pump Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.05 0.05 0.05 m3/h Air flow volume Sound pressure level dB(A) 40/38/36/33/30/27/25 42/40/38/37/35/32/25 48/46/44/41/37/35/32 (SH/H/MH/M/ML/L/SL) Output 0.03...
  • Page 25: Product Data Of Bu Module

    Super Free Match Service Manual 4.3 Product Data of BU Module Model FXB3A-K FXB5A-K Maximum numbers of connectable indoor units Power Supply V-Ph-Hz 220~240-1-50 Gas pipe(inner diameter) Φ15.9 Φ15.9 Connection port to Liquid pipe(inner diameter) Φ9.52 Φ9.52 outdoor unit Connection Method Flare Flare Gas pipe(inner diameter)
  • Page 26: Piping Diagram

    Super Free Match Service Manual 6 PIPING DIAGRAM Schematic Diagram of Super Free Match Series Inverter Heat Pump Multi System The units start to work once the power is switched on. During the cooling operation, the low temperature, low pressure refrigerant gas from the heat exchanger of each indoor unit gets together and then is taken into the compressor to be compressed into high temperature, high pressure gas, which will soon go to the heat exchanger of the outdoor unit to exchange heat with the outdoor air and then is turned into refrigerant liquid.
  • Page 27 Super Free Match Service Manual CONTROL CONTROL...
  • Page 28: Control

    Super Free Match Service Manual Control 1 OPERATION FLOWCHART CONTROL...
  • Page 29: Cooling/Dry Operation

    Super Free Match Service Manual 1.1 Cooling/Dry Operation Cooling Operation Is there Guide Louver? Guide Louvers Swing Fan Motor:Operation Is the process of preventing restart operation? (3 minutes) Temperature Adjustment Fan Motor: Stop Electronic Expansion Valve: Stop Electronic Expansion Valve:Capacity Conctrol Stop (Go to the previous page) CONTROL...
  • Page 30: Heating Operation

    Super Free Match Service Manual 1.2 Heating Operation CONTROL...
  • Page 31: Main Logic

    Super Free Match Service Manual 2 MAIN LOGIC 2.1 Control Function of Outdoor Unit 2.1.1 Cooling Mode Cooling conditions and process: If the compressor is in stop status and start the unit for cooling operation, when one of the indoor units reaches the cooling operation condition, the unit starts cooling operation;...
  • Page 32: Protection Function

    Super Free Match Service Manual The status of 4-way valve: energized; Outdoor fan control in heating mode The outdoor fan starts before 5s of the starting of compressor and then it will run in high speed for 40s; The fan shall run at every speed for at least 80s; When the compressor stops, the outdoor fan stops after 1min. Defrosting function When the defrosting condition is met, the frequency of the compressor starts to decrease and wait for defrosting;...
  • Page 33: Other Function

    Super Free Match Service Manual 2.2.4 Communication malfunction Detection of the quantity of installed indoor units and BU modules: After 3min of energizing, if the outdoor unit does not receive the communication data of certain indoor unit, the outdoor unit will judge that indoor unit is not installed and will treat it as it is not installed.
  • Page 34: Control Function Of Indoor Unit

    Super Free Match Service Manual 2.4 Control Function of Indoor Unit 2.4.1 Running Mode 1. COOL 2.DRY 3.HEAT 4.AUTO 5 FAN 2.4.2 Basic Functions of the System COOL Mode Under this mode, the fan and swing function goes as the set conditions, and the set temperature range is 16℃ ~30℃.
  • Page 35 Super Free Match Service Manual speed. d) Under the HEAT Mode: (Ambient temperature herein is the temperature without temperature compensation) ◆ When the ambient temperature is or lower than the set temperature, the indoor unit runs at the high speed. ◆...
  • Page 36 Super Free Match Service Manual c) When the indoor unit works without the wired controller, if the timer is not set for the last remote control instruction, the system will memorize this last instruction and works following it; if the timer is set, it will be canceled as the power failure occurs and will have to be reset.
  • Page 37: Remote Controller

    Super Free Match Service Manual 3 REMOTE CONTROLLER 3.1 Wired Remote Controller 3.1.1 Wired Controller XK19 It is designed for the cassette type, duct type and floor ceiling type indoor units. ◆ Outside View of the Wired Controller   ◆ LCD of the Wired Controller  ...
  • Page 38 Super Free Match Service Manual Master wired controller (this function is yet unavailable for this unit). It blinks under on state of the unit without operation of any button.   Energy-saving function.(this function is yet unavailable for this unit) Ambient/preset temperature value. Electric auxiliary heating function.(this function is yet unavailable for this unit) Blow function.
  • Page 39 Super Free Match Service Manual 3.1.3 Operation Instructions On/Off Press On/Off to turn on the unit and turn it off by another press. Mode Setting Under the “On” state of the unit, press Mode to switch the operation modes as the following sequence: Cooling-Dry-Fan-Heating.
  • Page 40 Super Free Match Service Manual b. 26℃ is the default Sleep curve temperature before delivery. The wired controller will automatically memorize the Sleep curve after the setting. Turbo Setting Turbo function: The unit at the high fan speed can realize quick cooling or heating so that the room temperature can quickly approach the setting value.
  • Page 41 Super Free Match Service Manual failure will resume its original running state upon power recovery. Memory contents: On/Off, Mode, set temperature, set fan speed, Save function and Lock function. Enquiry of the Outdoor Ambient Temperature Under the “On” or “Off” state of the unit, press Enter/Cancel for 5s, and the outdoor ambient temperature will be displayed after a sound of click.
  • Page 42: Wireless Remote Controller Yt1F (Moto)

    Super Free Match Service Manual 3.2 Wireless Remote Controller YT1F (MOTO) Notes: a. Be sure that there are no obstructions between the receiver and the remote controller; b. Do not drop or throw the remote controller; c. Do not let any liquid into the remote controller and expose the remote controller to direct sunlight or any place where is very hot.
  • Page 43 Super Free Match Service Manual Auto, Cool, Dry Fan, Heat modes can be selected circularly by pressing this button. Auto mode is the default after power on. Under Auto mode, the temperature will not be displayed. Under Heat mode, the initial value is 28 ℃(82℉);...
  • Page 44 Super Free Match Service Manual   If the swing function is deactivated when the air guide louver is swing up and down, it will stop at the current position indicates that the air guide louver swings up and down among all five positions.  ...
  • Page 45: Wireless Remote Controller Yaa1Fb1

    Super Free Match Service Manual ◆ X-FAN ON: When press the ON/OFF button to turn off the unit, the indoor fan will continue running for about another 10 minutes at the low speed. In this case, the indoor fan can be stopped directly by pressing the button X-FAN.
  • Page 46 Super Free Match Service Manual - Press this button to decrease set temperature. Holding it down above 2 seconds rapidly decreases set temperature. In AUTO mode, set temperature is not adjustable. + Press this button to increase set temperature. Holding it down above 2 seconds rapidly increases set temperature.
  • Page 47 Super Free Match Service Manual healthy function; LCD display “ ”. Press this button again to repeat the operation above. SLEEP: ◆ Press this button, can select Sleep 1 ( ), Sleep 2 ( ), Sleep 3 ( ) and cancel the Sleep, circulate between these, after electrified, Sleep Cancel is defaulted.
  • Page 48 Super Free Match Service Manual     (display " " signal) and Quiet OFF (there is no signal of " "displayed),after powered on, the Quiet OFF is defaulted. Note: the Quiet function cannot be set up in Fan and Dry mode; Under the Quiet mode  ...
  • Page 49: Wireless Remote Controller Yag1Fb

    Super Free Match Service Manual Combination of " TEMP " and "CLOCK" buttons : About Energy-saving Function Press “TEMP” and “CLOCK” simultaneously in COOL mode to start energy-saving function. Nixie tube on the remote controller displays “SE”. Repeat the operation to quit the function. Combination of "TEMP "...
  • Page 50 Super Free Match Service Manual   Press this button, Auto, Low, Medium-low, Medium, Medium-high, High speed can be circularly selected. After powered on, Auto fan speed is default. Under DRY mode, Low fan speed only can be set up.     Low fan Low-Medium fan Medium fan...
  • Page 51 Super Free Match Service Manual mode or fan speed. X-FAN: Pressing X-FAN button in COOL or DRY mode, the icon is displayed and the indoor fan will continue operation for 10(2) minutes in order to dry the indoor unit even though you have turned off the unit. After energization, X-FAN OFF is defaulted.
  • Page 52 Super Free Match Service Manual 15) TIMER ON   Timer On setting : Signal “ON” will blink and display, signal will conceal, the numerical section will become the timer on setting status. During 5 seconds blink, by pressing + or - button to adjust the time value of numerical section, every press of that button, the value will be increased or decreased 1 minute.
  • Page 53 Super Free Match Service Manual increased 1℃ in every hour, after 1℃ the temperature will be maintained, after 7hours, the temperature will be decreased 1℃, after that the unit will keep on running under this temperature; ④ When setting the initial temperature 30℃, under this temperature setting, after 7hours, the temperature will be decreased 1℃, after that the unit will keep on running under this temperature;...
  • Page 54 Super Free Match Service Manual Press LIGHT button, to control the on and off of the displaying part of the unit (This function may be not available for some units). Press TURBO button, can realize the ON and OFF of TURBO function. 3.4.4 Introduction for special Operation About X-FAN function This function indicates that moisture on evaporator of indoor unit will be blowed after the unit is stopped to...
  • Page 55: Wireless Remote Controller Yb1F2 (Xfan)

    Super Free Match Service Manual the operation to quit the function. About Quiet function When quiet function is selected: ① Under cooling mode: indoor fan operates at notch 4 speed. 10 minutes later or when indoor ambient temperature≤28℃, indoor fan will operate at notch 2 speed or quiet mode according to the comparison between indoor ambient temperature and set temperature.
  • Page 56 Super Free Match Service Manual   " " on indoor unit is ON (green indicator. Color may be different for different models) and indoor unit gives out a sound. MODE Press this button, Auto, Cool, Dry, Fan, Heat mode can be selected circularly.  ...
  • Page 57 Super Free Match Service Manual Low speed Medium speed High speed Note: Under AUTO Speed, indoor unit fan motor will adjust the fan speed (high, medium or low speed) according to ambient temperature. Fan speed under dry mode is low speed. SWING UP and DOWN  ...
  • Page 58 Super Free Match Service Manual Under cool mode, press SAVE button and the unit will operate under SAVE mode. Dual-8nixie tube on remote controller displays "SE". Air conditioner will operate at auto speed. Set temperature can’t be adjusted. Press SAVE button again to exit SAVE mode. Air conditioner turn back to original set speed and set temperature. This function is applicable to partial of models.
  • Page 59: Smart Zone Controller (Ce50-24/E)

    Super Free Match Service Manual Time interval between two operations can’t exceed 5s. Otherwise, remote controller will exit the setting status automatically. 11) TURBO When pressing this button under cooling or heating mode, air conditioner will enter into quick cooling or quick heating mode.
  • Page 60: Communication Network

    Super Free Match Service Manual 4.1.1 Function Introduction This smart zone controller is a kind of regional controller, which is designed for free match units, capable of controlling up to 3 outdoor units and 16 indoor units. Through this smart zone controller, it is available to view and control those running parameters of the indoor unit, including on/off, running mode, fan speed etc, and also perform the single control and centralized control, further, it also can set the weekly timer and long-distance shielding to realize convenient control to the air conditioning system.
  • Page 61: Lcd

    Super Free Match Service Manual   Note: The smart zone controller can connect with maximum up to 16 indoor units. 4.3 LCD     Name Description Fan speed It displays the fan speed of the indoor unit, high, medium, low and auto. Running mode It displays the running mode of the indoor unit, auto, cool, dry, fan and heat.
  • Page 62: Buttons

    Super Free Match Service Manual It displays “CENTER” under the centralized control mode and no display under Control mode the single control mode. Ambient temperature/ It displays the ambient temperature, serial port as well as symbols of Celsius and Serial port Fahrenheit scale.
  • Page 63 Super Free Match Service Manual It is used for the switchover between unit 4 and unit 12; Under the timing or clock setting Thu 4/12 status, it indicates Thursday. Fri 5/13 It is used for the switchover between unit 5 and unit 13; Under the timing or clock setting status, it indicates Friday.
  • Page 64 Super Free Match Service Manual INSTALLATION INSTALLATION...
  • Page 65: Installation

    Super Free Match Service Manual INSTALLATION 1 PRECAUTIONS FOR INSTALLATION 1.1 Precautions for Installation Before installation, please ensure the installing site, power ratings, possible operating range (pipe distance, height difference between indoor and outdoor unit, power voltage) and installing space are correct and suitable. To ensure correct installation, please make sure to read the Safety Considerations thoroughly before starting the installation works.
  • Page 66 Super Free Match Service Manual Do not use or store flammable, explosive, poisonous or other dangerous substances beside the air conditioner. The compressor will vibrate sharply if the voltage is too low and damage the refrigerating system. Electrical component are easy to damage if the voltage is too high. The voltage should be stable; there shouldn’t be big fluctuation Please take notice of the installation foundation of the unit after long use, if it is damaged, it may lead to the fall of the unit and cause the injury.
  • Page 67: Key Points Of Installation

    Super Free Match Service Manual 1.2 Key Points of Installation Installation Procedures Description and Acceptance Criteria ◆ The materials specified on the engineering drawing shall be purchased as specified (e.g. copper tube, thermal insulation tube, PVC pipe, power cables, air switch, etc). ◆...
  • Page 68 Super Free Match Service Manual acceptable if pressure drop is within 0.02MPa. (With the temperature change by 1 , the pressure will change by ℃ approx. 0.01MPa) ◆ The thermal insulation tube must meet the specifications. Thermal insulation ◆ Seal between the thermal insulation pipes to avoid air entry. ◆...
  • Page 69: Super Free Match Service Manual

    Super Free Match Service Manual 2 FLOW CHART OF INSTALLATION Design kicking-off Material selection Inspection of site installation position Installation of indoor unit Installation of outdoor unit Installation of BU module Installation of Connection of Connection of Connection of Connection of Connection of remote transmission...
  • Page 70: Outdoor Unit Installation

    Super Free Match Service Manual 3 OUTDOOR UNIT INSTALLATION 3.1 Precautions for R410A It is very strict that the refrigerant pipes should be clean and dry. The R410A is a mixed refrigerant, when add the refrigerant to the unit, it must keep the refrigerant in its liquid state.
  • Page 71: Parts And Components Of Unit

    Super Free Match Service Manual 3.5 Parts and Components of Unit For the super free match series system, one outdoor unit is able to drive up to three BU modules and nine indoor units which include cassette type, duct type, wall-mounted type, floor ceiling type and console type. The outdoor unit will run as long as any one indoor unit receives the running command, and all indoor units stop once the outdoor unit is turned off.
  • Page 72: Outline Dimension Of The Outdoor Unit

    Super Free Match Service Manual The place should be well-ventilated, so the machine can absorb and discharge sufficient air. Outdoor unit shall be installed close to the indoor unit, hence to minimize the length and bends of cooling pipe. Avoid place the outdoor unit under the windows or between the constructions, hence to prevent normal operating noise from entering the room.
  • Page 73: Installation Of The Outdoor Unit

    Super Free Match Service Manual 3.9 Installation of the Outdoor Unit Check the installation location and ensure it is strength and level, so that the unit will not cause any operating vibration or noise after installation. In accordance with the foundation drawing in the following figure, please drill 4 holes in the installation location.
  • Page 74: Indoor Unit Installation

    Super Free Match Service Manual 4 INDOOR UNIT INSTALLATION 4.1 Installation of Wall Mounted Type 4.1.1 Important Notices The installation of air conditioner unit must be in accordance with national and local safety codes. Installation quality will directly affect the normal use of air conditioner unit. The user is prohibited from installation by himself.
  • Page 75 Super Free Match Service Manual 4.1.5 Installation of Mounting Plate Mounting plate should be installed horizontally. As the water drainage pipe for the indoor unit is two-way type, during installation, the indoor unit should slightly slant to water tray's outlet for smooth drainage of condenser water.
  • Page 76: Installation Of Duct Type

    Where there is no corrosive gas, heavy dust, salt mist, smog or moisture. The unit which is installed in the following places is likely to run abnormally. If unavoidable, please contact the professional personnel at the GREE appointed service center: ① Where is full of oil;...
  • Page 77 Super Free Match Service Manual 4.2.3 Caution for Installation ◆ Ensure the hanger is strong enough to withstand the weight of the unit. ◆ The drainage of the drain pipe is easy. ◆ No obstacle is in the inlet/outlet and the air circulation is in good condition. ◆...
  • Page 78 Super Free Match Service Manual   4.2.6 Installation of the Indoor Unit Requirements on the Installation Location Ensure the hanger is strong enough to withstand the weight of the unit. The drainage of the drain pipe is easy. No obstacle is in the inlet/outlet and the air circulation is in good condition. Ensure the installation space shown in the following figures is left for the access to maintenance.
  • Page 79 Super Free Match Service Manual   Caution! Prior to the installation, please make a good preparation for all piping (refrigerant pipe, drain pipe) and wiring (wires of the wired controller, wires between the indoor and outdoor unit) of the indoor unit to make the further installation much easier.
  • Page 80 10 meters far away from the corresponding diffuser. The standard accessories supplied by GREE is the transition duct 200mm long and round air outlet φ200, however, those of other specifications can be purchased.
  • Page 81 Super Free Match Service Manual 4.2.9 Installation of the Return Air Duct 1) The default installation location of the rectangular flange is in the back and the return air cover plate is in the bottom.   2) If the downward return air is desired, just change the place of the rectangular flange and the return air cover plate.
  • Page 82 Super Free Match Service Manual 2) There is a condensate outlet on both left and right sides of the unit. Once one is confirmed to be used, the other should be clogged by a rubber plug, bundled by the binding wire and insulated by the insulation material to avoid water leakage.
  • Page 83 Super Free Match Service Manual 5) Insert the drain hose into the drain hole and tighten it with clamps. 6) Wrap the clamps with large amount of sponge for thermal insulation. 7) The drain hose inside the room also should be insulated. 4.2.13 Precautions for the Lift Pipe The installation height of the lift pipe should be less than 850mm.
  • Page 84: Installation Of Cassette Type

    Please contact the local Gree special nominated repair department before installation. Any malfunction caused by the unit that is installed by the department that is not special nominated by Gree would not deal with on time by the inconvenience of the business contact.
  • Page 85 Super Free Match Service Manual 4.3.3 Outline Dimension Drawings of the Indoor Unit   GKH(12)BA-K3DNA2A/I; GKH(18)BA-K3DNA2A/I     GKH(12)BA-K3DNA1A/I; GKH(18)BA-K3DNA1A/I; GKH(24)BA-K3DNA1A/I INSTALLATION...
  • Page 86 Super Free Match Service Manual 4.3.4 Installation and Servicing Space   The drilling of holes in the ceiling must be done by the professional personnel.   4.3.5 Installation of the Indoor Unit The primary step for install the indoor unit. When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper and lower of the hoisting stand to fix it.
  • Page 87 Super Free Match Service Manual Backout the install cardboard.   Note: Please do tighten the nuts and bolts to prevent air conditioner break off. 4.3.6 Drainage hose Install the drain hose The diameter of the drain hose should be equal or bigger than the connection pipe’s. (The diameter of polythene pipe: Outer diameter 25mm Surface thickness ≥...
  • Page 88 Super Free Match Service Manual   Drain stepup pipe note The install height of the drain raising pipe should less than 280mm. The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm.
  • Page 89: Installation Of Floor Ceiling Type

    Super Free Match Service Manual Check the smoothness of drain after installation. Check the drain state by immitting 600cc water slowly from the outlet vent or test hole. Check the drain in the state of refrigerating after installation of the electric circuit.  ...
  • Page 90 Please contact the local Gree special nominated repair department before installation. Any malfunction caused by the unit that is installed by the department that is not special nominated by Gree would not deal with on time by the inconvenience of the business contact.
  • Page 91 Super Free Match Service Manual It should be done by professional personnel when the air conditioner unit is moved to other place. 4.4.6 There are 2 styles of installation Ceiling type and Floor type Each type is similar to the other as follows: Determine the mounting position on ceiling or wall by using paper pattern to indicate indoor frame.
  • Page 92: Installation Of Console Type

    Super Free Match Service Manual In case of hanging It is possible to install using inward facing hanger brackets by not removing the brackets from the indoor unit. (Refer to ⑧) Be sure to use only the specified accessories and parts for installation work.  ...
  • Page 93 Super Free Match Service Manual 4.5.3 There are 2 styles of installation Ceiling type and Floor type Each type is similar to the other as follows: The indoor unit should be sited in a place where: the restrictions on installation specified in the indoor unit installation drawings are met. Both air intake and exhaust have clear paths met.
  • Page 94 Super Free Match Service Manual 4.5.6 Installation and Servicing Space     4.5.7 Installation of the Indoor Unit Preparation Open the front panel, remove the 4 screws and dismount the front grille while pulling it forward. Follow the arrows to disengage the clasps on the front case to remove Follow the procedure below when removing the slit portions.
  • Page 95 Super Free Match Service Manual Installation Secure using 6 screws for floor installations.(Do not forget to secure to the rear wall.) For wall installations, secure the mounting plate using 5 screws and the indoor unit using 4 screws. The mounting plate should be installed on a wall which can support the weight of the indoor unit. Temporarily secure the mounting plate to the wall, make sure that the panel is completely level, and mark the boring points on the wall.
  • Page 96 Super Free Match Service Manual Remove the air filters and pour some water into the drain pan to check the water flows smoothly.   Insert the supplied C drain hose into the socket of the drain pan. Fully insert the drain hose until it adheres to a seat of the socket.  ...
  • Page 97: Bu Module Installation

    Super Free Match Service Manual 5 BU MODULE INSTALLATION 5.1 Precaution for Installation The installation of the air conditioner must be in accordance with the national and local laws and regulations. The quality of the installation will affect the capability of air conditioner directly. The installation should be left to the appointed service center.
  • Page 98: Outline Dimension And Servicing Space Of Fxb3A-K

    Super Free Match Service Manual Installation at the following places might lead to the air conditioner malfunction. If it is unavoidable, please contact the appointed service center. A place which is full of machine oil; A region with saline-sodic soil near the sea; A place where the sulphide fog exists, such as the sulphur spring;...
  • Page 99: Outline Dimension And Servicing Space Of Fxb5A-K

    Super Free Match Service Manual 5.5 Outline Dimension and Servicing Space of FXB5A-K Outline dimension Sorts Indoor unit side (mm) Outdoor unit side (mm) Liquid pipe Φ6.35 Φ9.52 Gas pipe Φ9.52 Φ15.9 Installation and service space ① ② ③ Name Servicing space Ceiling Electrical box side...
  • Page 100: Installation Instruction

    Super Free Match Service Manual 5.6 Installation Instruction Check the installation location and ensure it is strength and level. Otherwise, there should be enough space to install drainage pipe, so that the condensed water can be discharged. Reference to the size of hanger metal and drill 4 holes in the installation location. Hang the hanger bolts.
  • Page 101: Refrigeration Piping Work

    6 REFRIGERATION PIPING WORK 6.1 Allowable Length and Drop Height of Connecting Pipe The sorts The pipes Length(m) Total length between outdoor unit and BU L1+L2+L3+L4+L5 ≤55 modules Total length GWHD(48S)NM3CO ≤80 Maximum 1A+1B+1C+2A+2B+2C+ between indoor allowable 3A+3B GWHD(56S)NM3CO ≤90 unit and BU...
  • Page 102: Connection Of Branch Pipe

    Super Free Match Service Manual 6.3 Connection of Branch Pipe If two or three BU modules used, Y-type branch pipe of FQ01A/A will be chosen. FQ01A/A (Liquid pipe) FQ01A/A (Gas pipe) Y-type branch pipe is equipped with auxiliary tubes to adjust the diameter of different pipes. If the dimension of the pipe selected is different from the dimension of branch pipe joint, Cut copper tube in the middle with tube cutter and clear up burrs.
  • Page 103 Super Free Match Service Manual ⑤ See the schematics below: Outdoor unit lower than indoor unit Outdoor unit higher than indoor unit INSTALLATION...
  • Page 104: Connection Of Outdoor Unit Refrigerant Pipe

    Super Free Match Service Manual 6.5 Connection of Outdoor Unit Refrigerant Pipe   ① ② ③ ④ Name Coping plate Rear side plate Front side plate Gas side stop valve ⑤ ⑥ ⑦ Name Liquid side stop valve Right connection board Front connection board Name Front connection...
  • Page 105: Precaution For Connection

    Super Free Match Service Manual Install the piping adapter ① Refer to the piping connection size of the outdoor unit and indoor units, the appropriate piping adapter should be adopted. ② Align the flared end of copper tube with the center of pipe joint. Tighten the nuts with hands. Sealing the unconnected port If the port of BU module indoor side does not connected to one indoor unit, the port must be sealed to prevent refrigerant leaks.
  • Page 106 Super Free Match Service Manual ② The bending diameter of the pipeline must be greater than 200mm. The connection pipe cannot often be bent or straightened. Otherwise it will harden and crack. ③ If the thermal insulation of the refrigerant pipe is not removed, please do not bend the pipe. Otherwise, it maybe leads the pipe to crack.
  • Page 107: Leak Test

    Super Free Match Service Manual 6.8 Leak Test Please make sure that the stop valves of the outdoor unit are closed during the operation. The leak test should be made by pressurizing nitrogen gas. Turn on the Hi-knob and Lo-knob. The leak test should be done simultaneously at both the gas and liquid stop valves.
  • Page 108: Refrigerant Charging

    Super Free Match Service Manual 6.10 Refrigerant Charging The refrigerant has been charged into the outdoor unit before shipped from the manufacturer, while additional refrigerant still need be charged into the refrigerant pipe during the field installation. 6.10.1 Calculation of the Additional Refrigerant Charging 1) Get the refrigerant charge of the outdoor unit from the nameplate.
  • Page 109 Super Free Match Service Manual The total length of the liquid pipes: 20+10+10+5+5+5+5+5+5=70(m). Thus, the total length is over than 30m, so the air conditioner needs to add refrigerant. Additional refrigerant charge Σ Σ the Liquid Pipe Length of Φ6.35×0.022kg/m + the Liquid Pipe Length of Φ9.52×0.054kg/m-1.47(kg) =(5+5+5+5+5+5)(m)×0.022kg/m+(20+10+10)(m)×0.054kg/m-1.47(kg) =1.35(kg)
  • Page 110 Super Free Match Service Manual c) Turn off the R410A tank and the Hi-knob immediately, when adding refrigerant is enough. Cautio ! Make sure the liquid and gas side stop valves are opened completely after the installation. Make sure the length of liquid pipe is exactly. Additional refrigerant charge must be measured exactly.
  • Page 111: Electrical Wiring Work

    Super Free Match Service Manual 7 Electrical Wiring Work 7.1 Wiring Connection Precept 1 Precept 2 INSTALLATION...
  • Page 112: Requirements Of Power Circuit And Cable

    7.2 Requirements of Power Circuit and Cable Frequency 50Hz Outdoor unit 3Ph, 380~415V Phase and voltage BU module 1Ph, 220V GWHD(48S)NM3CO Recommended cable of outdoor unit 5×2.5 mm (Pieces × Sectional area) GWHD(56S)NM3CO Recommended cable of BU module 3×0.75 mm (Pieces × Sectional area) Transmission line (Pieces ×...
  • Page 113: Precaution Of Laying Wires

    Super Free Match Service Manual device of the building by the professional. The electric installation should be carried out by the professional as instructed by the local laws, regulations and also this manual. The air switch coupled with the leakage current protection switch must be equipped in the circuits, which is of enough capacity and of both magnetic and thermal tripping functions in case of the short circuit and overload.
  • Page 114: Electrical Wiring Work For Bu Module

    Super Free Match Service Manual The power wire and transmission line must be more than one meter away from televisions or radios which can emit electromagnetic waves to prevent image interference or noise. Otherwise, the unit maybe cannot work. Confirm the each cable connected to the terminal screw is exactly and securely after finishing the electric work.
  • Page 115 Super Free Match Service Manual and transmission line from damaging by the hole, the rubber ring cannot fall from that, otherwise, it may cause electrical shock or fire etc. Connect the power cable of the BU module to the L, N terminals with the sign of Power and as well as the ground screw.
  • Page 116: Instructions For Dip Switch

    Super Free Match Service Manual 7.8 Instructions for DIP Switch 2 digits DIP is adopted to assign the address when using multi-BU modules and the address cannot be repeated in the same unit. One outdoor unit can connect to no more than 3 BU modules. “ON”...
  • Page 117: Installation Of Drainage Pipeline

    Super Free Match Service Manual 8 INSTALLATION OF DRAINAGE PIPELINE 8.1 Material Quality Requirements for Condensate Pipe Generally, the condensate pipe shall be water supply U-PVC pipe, adhered by using special glue. The other materials available include: PP-R pipe, PP-C pipe and hot-dipped galvanized steel pipe. It is not allowed to use aluminum plastic composite pipe.
  • Page 118 Super Free Match Service Manual if the drainage is smooth; on another hand, check the piping system for any leakage. Steel sheath shall be provided to the pipe crossing the wall or slab. The pipe joint shall not be positioned within the sheath.
  • Page 119 Super Free Match Service Manual matter how forcible it pushes, but there is no flowing water, thus resulting in abnormal water level. This will cause flooding of the ceiling.   15) If the air flow of indoor unit is high, this might cause negative pressure and result in return suction of outdoor air.
  • Page 120 Super Free Match Service Manual NO2: Connection of drain elbow   NO3: Connection of horizontal pipe   Drainage pipe is requisite for air conditioner unit. During cooling, the moisture in the air will condense on the surface of evaporator. Such condensing water must be drained out of the unit. Meanwhile, the drainage pipe has an important role to determine if the air conditioner can plays its full functions.
  • Page 121: Installation Of Protective Layer On Connection Pipe

    Super Free Match Service Manual 9 Installation of Protective Layer on Connection Pipe The refrigerant pipes should be insulated by the heat insulation material and plastic tape in order to prevent water condensation and leakage. Do not use the foam on the branch pipe as the material for heat insulation. The heat insulation material: Heat resistance to 100 ℃...
  • Page 122 Super Free Match Service Manual MAINTENANCE MAINTENANCE...
  • Page 123: Maintenance

    Super Free Match Service Manual MAINTENANCE 1 Testing Board Introduction 1.1 Compose of Testing Board The testing board is in front of electrical box and can be observed well. It has several following advantages: detect indoor unit numbers and indoor unit address, displays real running function and error code automatically. It is composed of the function section, data section and button section.
  • Page 124: Process Control Setting

    Super Free Match Service Manual 1.3 Process Control Setting 1.3.1 Button section + - Enter Back Signification Function Increase Decrease Enter Back Caution! ① When entering the menu to set parameters, the function section will flash running codes and the data section will flash the current parameters.
  • Page 125 Super Free Match Service Manual Back: Press “Back” key to the previous menu, and long press the “Back” key to exit the operation. ③ Display unit 1(d1) operation: When entering into the display unit 1: The function section display running code uninterrupted and the data section display the current value uninterrupted.
  • Page 126 Super Free Match Service Manual ④ Press “Enter” key: the function section display “Fo” code uninterrupted and the data section flashes the current parameters. ⑤ Switch with the “+” “-” to the target value, and then press “Enter” key: the function section display “Fo”...
  • Page 127: Troubleshooting

    Do not repair the air conditioner personally but instead contact the professionally skilled personnel at the GREE appointed service center, as the incorrect repair would cause electric shock or fire hazard etc. 2.1 Check before Contacting Maintenance Serviceman Please check the following items before contacting the maintenance serviceman.
  • Page 128: Problem Handling

    Super Free Match Service Manual 2.2 Problem Handling The conditions listed below are not classified into errors. Conditions Causes When restart the unit soon after it The overload protection switch of the unit let the The unit does not run is stopped startup delayed for three minutes As soon as power supply is on...
  • Page 129 Super Free Match Service Manual Compressor power protection Flash 21 times Compressor overload protection Flash 22 times Compressor discharge temperature Flash 23 times protection Lack of refrigerant or jam protection Flash 31 times Normal operation Flash 1 time Frequency limitation for AC current Flash 2 times Oil returning Flash 3 times...
  • Page 130 Super Free Match Service Manual Running mode conflicts indoor Communication error unit address Communication error between the main board and driving board Communication error between the main board and testing board Gas sensor error of indoor unit Humidity sensor error of indoor unit Water full error of indoor unit Jumper terminal error of indoor unit Phase lack of power supply...
  • Page 131: Flow Chart Of Troubleshooting

    Super Free Match Service Manual 3 FLOW CHART OF TROUBLESHOOTING Service personnel shall collect the malfunction information as much as possible and research them thoroughly, list these electrical parts which may cause malfunction, and shall be able to determine the specific reason and solve the faulted parts.
  • Page 132: Malfunction Display: Low Pressure Protection

    Super Free Match Service Manual 3.2 Malfunction display: Low Pressure Protection Low pressure protection Replace the outdoor unit mainboard Check the Check the pressure with a manometer: low pressure sensor: is Replace the low pressure sensor is it really low? it normal? Check Charge refrigerant according to the amount specified in the...
  • Page 133: Malfunction Display: Discharge Temperature Protection

    Super Free Match Service Manual 3.3 Malfunction display: Discharge temperature protection Discharge temperature protection Measure Measure the resistance value of discharge Replace the oudoor discharge temperature: does it have temperature sensor: is it unit mainboard reached 125℃? correct(50KΩ)? Replace relevant discharge temperature sensor Are the Replace relevant electronic...
  • Page 134: Malfunction Display: Communication Error

    Super Free Match Service Manual 3.5 Malfunction display: Communication error Communication error Check the Check the orientation of plug cable of indoor unit: is it and socet properly connected? Check the Check the orientation of plug transmission line between outdoor unit and BU module: is it properly and socet connected?
  • Page 135: Malfunction Display: Indoor Unit Water Full Protection

    Super Free Match Service Manual 3.6 Malfunction display: Indoor unit water full protection Water full protection Maintain the liquid level switch Check the Replace the mainboard of the Voltage of liquid level Is the water overflow? indoor unit switch : is it ok? Check the Check the Maintain the cables of water...
  • Page 136: Malfunction Display: High/Low Pressure Sensor Error

    Super Free Match Service Manual 3.8 Malfunction display: High/Low pressure sensor error Pressure sensor error The plug on pressure sensor is correctly Check the orientation of connected to the socket on plug and socket mainboard, is it? Measure the DC voltage value between black Replace the pressure line and green line of the sensor: is it sensor...
  • Page 137: Wiring Diagram

    Super Free Match Service Manual 4.2 Wiring diagram Note: This drawing is just for reference; please always refer to the electric wiring stuck to the unit for actual wiring. 4.2.1 Outdoor unit GWHD(56S)NM3CO、GWHD(48S)NM3CO MAINTENANCE...
  • Page 138 Super Free Match Service Manual 4.2.2 Indoor unit Wall mounted type ◆ Hansol GWH(07)TA-K3DNA1E/I; GWH(09)TA-K3DNA1E/I; GWH(12)TB-K3DNA1E/I; GWH(18)TC-K3DNA1E/I   GWH(28)TD-K3DNA1C/I   MAINTENANCE...
  • Page 139 Super Free Match Service Manual ◆ U-Cool GWH(07)UA-K3DNA1B/I; GWH(09)UA-K3DNA1B/I; GWH(12)UB-K3DNA1B/I; GWH(18)UC-K3DNA1B/I   ◆ Cozy GWH(07)MA-K3DNA3E/I; GWH(09)MA-K3DNA3E/I; GWH(12)MB-K3DNA3E/I;GWH(18)MC-K3DNA3E/I MAINTENANCE...
  • Page 140 Super Free Match Service Manual ◆ Change GWH(07)KF-K3DNA6E/I; GWH(09)KF-K3DNA6E/I; GWH(12)KF-K3DNA6E/I; GWH(18)KG-K3DNA6E/I ◆ Viola GWH(07)RA-K3DNA3E/I; GWH(09)RA-K3DNA3E/I; GWH(12)RB-K3DNA3E/I; GWH(18)RC-K3DNA3E/I; GWH(24)RC-K3DNA1A/I   MAINTENANCE...
  • Page 141 Super Free Match Service Manual Duct type GFH(09)EA-K3DNA1A/I; GFH(12)EA-K3DNA1A/I; GFH(18)EA-K3DNA1A/I; GFH(21)EA-K3DNA1A/I; GFH(24)EA-K3DNA1A/I Cassette type GKH(12)BA-K3DNA2A/I; GKH(18)BA-K3DNA2A/I;   MAINTENANCE...
  • Page 142 Super Free Match Service Manual GKH(12)BA-K3DNA1A/I; GKH(18)BA-K3DNA1A/I; GKH(24)BA-K3DNA1A/I   Floor ceiling type GTH(09)BA-K3DNA1A/I; GTH(12)BA-K3DNA1A/I; GTH(18)BA-K3DNA1A/I; GTH(24)BA-K3DNA1A/I   MAINTENANCE...
  • Page 143 Super Free Match Service Manual Console type GEH(09)AA-K3DNA1C/I; GEH(12)AA-K3DNA1C/I; GEH(18)AA-K3DNA1C/I   MAINTENANCE...
  • Page 144 Super Free Match Service Manual 4.2.3 BU module FXB3A-K MAINTENANCE...
  • Page 145 Super Free Match Service Manual FXB5A-K MAINTENANCE...
  • Page 146: The Resistances Of Common Temperature Sensors

    Super Free Match Service Manual 5 THE RESISTANCES OF COMMON TEMPERATURE SENSORS 5.1 15 KΩ Temp. Resistance Voltage Voltage Temp. Resistance Voltage Voltage (℃) (kΩ) (15K/5V) (15K/3.3V) (℃) (kΩ) (15K/5V) (15K/3.3V) 144.000 0.472 0.311 18.750 2.222 1.467 138.100 0.490 0.323 17.930 2.278 1.503...
  • Page 147: 20 Kω

    Super Free Match Service Manual Temp. Resistance Voltage Voltage Temp. Resistance Voltage Voltage (℃) (kΩ) (15K/5V) (15K/3.3V) (℃) (kΩ) (15K/5V) (15K/3.3V) 3.579 4.037 2.664 2.998 4.167 2.750 3.454 4.064 2.682 2.898 4.190 2.766 3.333 4.091 2.700 2.797 4.214 2.781 3.217 4.117 2.717 2.702...
  • Page 148: 50 Kω

    Super Free Match Service Manual Temp. Resistance Voltage Voltage Temp. Resistance Voltage Voltage (℃) (kΩ) (15K/5V) (15K/3.3V) (℃) (kΩ) (15K/5V) (15K/3.3V) 13.59 2.977 1.965 5.942 3.855 2.544 13.04 3.027 1.998 5.726 3.887 2.565 12.51 3.076 2.030 5.519 3.919 2.586 3.125 2.063 5.32 3.949...
  • Page 149 Super Free Match Service Manual Temp. Resistance Voltage Voltage Temp. Resistance Voltage Voltage (kΩ) (15K/5V) (15K/3.3V) (kΩ) (15K/5V) (15K/3.3V) (℃) (℃) 145.42 0.322 0.212 21.425 1.591 1.050 138.26 0.337 0.223 20.601 1.634 1.078 131.5 0.353 0.233 19.814 1.677 1.107 126.17 0.367 0.242 19.061...
  • Page 150 Super Free Match Service Manual Temp. Resistance Voltage Voltage Temp. Resistance Voltage Voltage (℃) (kΩ) (15K/5V) (15K/3.3V) (℃) (kΩ) (15K/5V) (15K/3.3V) 4.7541 3.389 2.237 2.4983 4.001 2.640 4.6091 3.423 2.259 2.4308 4.022 2.655 4.4693 3.456 2.281 2.3654 4.044 2.669 4.3345 3.488 2.302 2.3021...
  • Page 151: Disassembly And Assembly Procedure Of Main Parts

    Super Free Match Service Manual 6 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS 6.1 Outdoor Unit 6.1.1 Disassembly and Assembly of the plates Remarks: Prior to the assembly of the plates, make sure the power supply is cut off. Steps Illustrations Operation Instructions  ...
  • Page 152 Super Free Match Service Manual Unscrew the fixed screws of 4.Disconnect the left left side plate and rear side side plate and rear side plate; plate Remove left side plate and rear side plate. 6.1.2 Assembly and Disassembly of the Compressor Remarks: Prior to the assembly of the compressor, make sure there is no refrigerant in the pipeline and the power supply is cut off.
  • Page 153 Super Free Match Service Manual 3.Loose the fixed Unscrew the fixed screws of the screw of the compressor compressor base base   Remove and replace the compressor. 4.Remove the Note: never let the flame compressor away contact any other from the seating component during the replacement.
  • Page 154 Super Free Match Service Manual Solder the connecting 6.Solder the pipe to make them pipeline with the connected suction and Note: never let the discharge ports of flame contact any other the compressor component. Tighten the fixing screw of the power cord.
  • Page 155 Super Free Match Service Manual 6.1.3 Disassembly and Assembly of 4-way valve Remarks: Prior to the assembly of the compressor, make sure there is no refrigerant in the pipeline and the power supply is cut off. Steps Illustrations Operation Instructions a) Unscrew the fixed screws of the magnet 1.Remove the magnet...
  • Page 156: Indoor Unit

    Super Free Match Service Manual 6.2 Indoor unit 6.2.1 Wall mounted type ◆ Removal and Assembly of Fan Motor Remark: Prior to the assembly of the motor, make sure the power supply is cut off. Steps Illustrations Operation Instructions Loosen the screws;  ...
  • Page 157 Super Free Match Service Manual   Remove the filter 2.Remove the screen cover plate for Unscrew the fixed return air screws of the return   Undo the buckle of the 3.Remove the rear rear and front volutes and volute then remove the rear volute away.
  • Page 158 Super Free Match Service Manual Separate the motor   away from the motor support. Remove the fan blade Remove the Take the motor out motor away. from the return air frame Note: the motor support shall be removed in advance and then changed to the unit.
  • Page 159: Remove The

    Super Free Match Service Manual 3.Unscrew the fixed Unscrew the fixed bolts of bolts of the fan the fan with the spanner 4.Remove the fan Remove the fan 5.Loosen the fixed bolts Loosen the fixed bolts of of the fan motor the fan motor MAINTENANCE...
  • Page 160 Super Free Match Service Manual 6.Remove the motor and Remove the motor and replace it replace it 7.Screw the fixed bolts Screw the fixed bolts of the of the motor motor 8.Mount the fan and Mount the fan and screw screw the fixing bolts the fixing bolts MAINTENANCE...
  • Page 161: Unscrew The Fixed Screws Of The Water Tray

    Super Free Match Service Manual   9.Mount the water tray Mount the water tray and and screw the screws screw the screws Removal and Assembly of drainage pump ◆ Remark: Prior to the assembly of the drainage pump, make sure the power supply is cut off. Steps Illustrations Operation Instructions...
  • Page 162 Super Free Match Service Manual 4.Take out the pump and Take out the pump and replace it replace it Connect the drainage Connect the drainage pipe pipe and screw the fixed and screw the fixed screws screws the water pump. the water pump.
  • Page 163 Super Free Match Service Manual 6.2.4 Floor ceiling type Remark: Prior to the assembly of the indoor unit, make sure the power supply is cut off. ◆ Removal panel grating module Steps Illustrations Operation Instructions Move down the clip of the  ...
  • Page 164 Super Free Match Service Manual ◆ Remove air deflecting plate modules Steps Illustrations Operation Instructions Remove the air deflecting   plates from the air deflecting plate support assembly, and then remove both ends from Remove sub-assy of the air sweeping motor. joint air deflecting plate (As is shown in the graph, arrow represents the support...
  • Page 165 Super Free Match Service Manual ◆ Remove fixing plate sub-assy for air sweeping fans Steps Illustrations Operation Instructions   Remove fixing plate Remove the screws shown sub-assy for air in the graph sweeping fans ◆ Remove fan and motor components Steps Illustrations Operation Instructions...
  • Page 166: Exploded Views And Part List

    Super Free Match Service Manual 7 EXPLODED VIEWS AND PART LIST 7.1 Outdoor unit GWHD(48S)NM3CO; GWHD(56S)NM3CO   MAINTENANCE...
  • Page 167 Super Free Match Service Manual Part list: GWHD(48S)NM3CO GWHD(56S)NM3CO Description Code Code Rear Grill 01574100004 01574100004 Condenser Assy 01124100088 01124100088 Clap board 01244100005 01244100005 Coping Plate 01264100008P 01264100008P Electrical Box 01395200247 01395200248 Reactor Box Cover 01424100030 01424100030 Reactor 43130179 43130179...
  • Page 168 Super Free Match Service Manual Nozzle for Adding Freon 06120012 06120012 Low pressure sensor 322101001 322101001 Electronic Expansion Valve Sub-assy 43044100022 43044100022 Check Valve 07130101 07130101 Capillary Sub-assy (oil returning) 04004100011 04004100011 Pressure regulating valve 07334100002 07334100002 Electromagnetic Valve 43000054 43000054 Magnet Coil 4304000415...
  • Page 169: Indoor Unit

    Super Free Match Service Manual 7.2 Indoor unit 7.2.1 Wall mounted type ◆ Hansol GWH(07)TA-K3DNA1E/I;GWH(09)TA-K3DNA1E/I; GWH(12)TB-K3DNA1E/I; GWH(18)TC-K3DNA1E/I Part list: GWH(07)TA-K3DNA1E/I for CB148N05201; GWH(09)TA-K3DNA1E/I for CB148N05301 GWH(12)TB-K3DNA1E/I for CB148N05401; GWH(18)TC-K3DNA1E/I for CB148N05501 GWH(07)TA-K3DNA1E/I GWH(12)TB-K3DNA1E/ GWH(18)TC-K3DNA1E Description GWH(09)TA-K3DNA1E/I Code Code Code Front Panel 20012853 20012849 20012820U...
  • Page 170 Super Free Match Service Manual Left Axile Bush 10512037 10512037 1051203701 Propeller Axile Bush 1054202101 1054202101 1054204701 Evaporator Support 24212114 24212114 24212139 Cold Plasma 1114001602 1114001602 1114001601 Generator Evaporator Assy 0100233801 0100294502 0100238601 Cross Flow Fan 10352038 10352033 10352045 Drainage Hose 0523001408 05230014 0523001406...
  • Page 171 Super Free Match Service Manual GWH(28)TD-K3DNA1C/I Part list: GWH(28)TD-K3DNA1C/I CB148N07900 GWH(28)TD-K3DNA1C/I Description Code Front Panel 20012894U Filter Sub-Assy 11122136 Screw Cover 242520053 Front Case Sub-assy 20022004 Guide Louver 10512236 Guide Louver (small) 1051223701 Swing Lever 2 1058211601 Air Louver 10512252 Left Axile Bush 1051203701 Water Tray Assy...
  • Page 172 Super Free Match Service Manual O-Gasket of Cross Fan Bearing 76512203 Left Evaporator Support 24212041 Evaporator Assy 01002340 Wall Mounting Frame 01252398 Right Evaporator Support 2421204201 Fan Motor 1501213401 Motor Fixed Clip1 26112324 Motor Fixed Clip2 26112325 Pipe Clamp 26112071 Fixed Clip(Evaporator) 02112009 Drainage Hose...
  • Page 173 Super Free Match Service Manual ◆ U-Cool GWH(07)UA-K3DNA1B/I; GWH(09)UA-K3DNA1B/I; GWH(12)UB-K3DNA1B/I; Part list: GWH(07)UA-K3DNA1B/I for CB204N02600; GWH(09)UA-K3DNA1B/I for CB204N02700; GWH(12)UB-K3DNA1B/I for CB204N02800 GWH(07)UA-K3DNA1B/I GWH(12)UB-K3DNA1B/I Description GWH(09)UA-K3DNA1B/I Code Code Front Panel Sub-Assy 2001269506 2001285901 Filter Sub-Assy 11122122 11122134 Screw Cover 24252024 24252024 Front Case Sub-assy 20022424 2001272701...
  • Page 174 Super Free Match Service Manual Axile Bush Sub-assy 10542024 10542024 Evaporator Support 24212132 24212128 Evaporator Assy 0100263001 0100229401 Shield Board (Elbow) 01382010 01382010 Wall Mounting Frame 01252121 01252121 Motor Press Plate 26112270 26112261 Fan Motor 15012125 150120874 Pipe Clamp 26112164 26112164 Rubber Plug (Water Tray) 76712012...
  • Page 175 Super Free Match Service Manual GWH(18)UC-K3DNA1B/I   Part list: GWH(18)UC-K3DNA1B/I for CB204N02900 GWH(18)UC-K3DNA1B/I Description Code Front Panel Assy 2001280401 Filter Sub-Assy 11122133 Screw Cover 24252024 Front Case Sub-assy 2001280503 Guide Louver 2 10512223 Guide Louver 1 10512222 Shaft of guide louver 1054202001 Air Louver(Manual) 10512221...
  • Page 176 Super Free Match Service Manual Cross Flow Fan 10352030 Evaporator Support 24212135 Evaporator Assy 01002442 Cold Plasma Generator 1114001603 Shield board (elbow) 01382010 Wall Mounting Frame 01252032 Motor Press Plate 26112295 Fan Motor 1501209802 Connecting pipe clamp 26112164 Stepping Motor 15212125 Stepping Motor 15212126...
  • Page 177 Super Free Match Service Manual ◆ Cozy GWH(07)MA-K3DNA3E/I; GWH(09)MA-K3DNA3E/I; GWH(12)MB-K3DNA3E/I Part list: GWH(07)MA-K3DNA3E/I for CB171N08600; GWH(09)MA-K3DNA3E/I for CB171N08501; GWH(12)MB-K3DNA3E/I for CB171N08701 GWH(07)MA-K3DNA3E/I GWH(12)MB-K3DNA3E/I Description GWH(09)MA-K3DNA3E/I Code Code Receiver Window 20192229 22432230 Front Panel Assy 20012241 20012548 Filter Sub-Assy 11122081 1112220403 Screw Cover 24252016 24252016...
  • Page 178 Super Free Match Service Manual Rear Case assy 2220210111 2220210301 Rubber Plug (Water Tray) 76712012 76712012 Ring of Bearing 26152022 26152022 O-Gasket sub-assy of Bearing 7651205102 7651205102 Cross Flow Fan 10352018 10352017 Remote Controller 305100491 305100491 Temperature Sensor 390000599 390000599 Ambient Temperature Sensor 390000453 '390000453...
  • Page 179 Super Free Match Service Manual GWH(18)MC-K3DNA3E/I Part list: GWH(18)MC-K3DNA3E/I for CB171N08401 GWH(18)MC-K3DNA3E/I Description Code Receiver Window 22432173 Front Panel Assy 20012260 Filter Sub-Assy 1112208901 Screw Cover 24252016 Baffle Plate 26112228 Front Case Sub-Assy 20022172 Air Louver 2 10512117 Air Louver 1 10512116 Helicoid tongue 26112238...
  • Page 180 Super Free Match Service Manual Ring of Bearing 26152022 O-Gasket sub-assy of Bearing 7651205102 Cross Flow Fan 10352019 Remote Controller 305100491 Temperature Sensor 390000599 Ambient Temperature Sensor 390000453 Connecting Cable 4002052317 Evaporator Support 24212133 Evaporator Assy 01002774 Wall Mounting Frame 01252218 Motor Press Plate 26112494...
  • Page 181 Super Free Match Service Manual ◆ Change GWH(07)KF-K3DNA6E/I;GWH(09)KF-K3DNA6E/I;GWH(12)KF-K3DNA6E/I; GWH(18)KG-K3DNA6E/I Part list: GWH(07)KF-K3DNA6E/I for CB146N26201; GWH(09)KF-K3DNA6E/I for CB146N26301; GWH(12)KF-K3DNA6E/I for CB146N26401; GWH(18)KG-K3DNA6E/I for CB146N26501 GWH(07)KF-K3DNA 6E/I GWH(12)KF-K3DNA6 GWH(18)KG-K3DN Description GWH(09)KF-K3DNA A6E/I 6E/I Code Code Code Membrane 63062017 63062017 63062022 Front Panel Assy 20012443S 20012443S 20012495S...
  • Page 182 Super Free Match Service Manual Guide Louver 10512119 10512119 10512140 Shaft of guide louver 1054202001 1054202001 10512037 Air Louver 10512160 10512160 10512160 Helicoid tongue 26112486 26112486 26112232 Rear Case assy 2220229501 2220229501 22202154 Pipe plug (outlet) 76712020 76712020 76712012 Axile Bush sub-assy 10542024 10542024 10542047...
  • Page 183 Super Free Match Service Manual ◆ Viola GWH(07)RA-K3DNA3E/I;GWH(09)RA-K3DNA3E/I;GWH(12)RB-K3DNA3E/I;GWH(18)RC-K3DNA3E/I Part list: GWH(07)RA-K3DNA3E/I for CB302N01501; GWH(09)RA-K3DNA3E/I for CB302N01601; GWH(12)RB-K3DNA3E/I for CB302N01701; GWH(18)RC-K3DNA3E/I for CB302N01801 GWH(07)RA-K3DNA3E/I GWH(12)RB-K3DNA3E/I GWH(18)RC-K3DNA3E/I Description GWH(09)RA-K3DNA3E/I Code Code Code Front Panel Assy 20012878 20012858 20012760 Display Board 30565137 30565137 30565121 Filter Sub-Assy 11122206...
  • Page 184 Super Free Match Service Manual Guide Louver 10512204 10512203 10512205 Air Louver 1 1051211302 1051215603 1051211602 Air Louver 2 1051211402 1051215503 1051211702 Helicoid Tongue 2611216202 2611216302 2611223802 Axile Bush 10542036 10542036 10542036 Rear Case assy 22202186 22202467 22202193 Cross Flow Fan 10352018 10352017 10352019...
  • Page 185 Super Free Match Service Manual GWH(24)RC-K3DNA1A/I Part list: GWH(24)RC-K3DNA1A/I for CB144N01100 GWH(24)RC-K3DNA1A/I Description Code Front Panel Assy 20012734 Filter Sub-Assy 11122091 Screw Cover 24252016 Front Case 2001297002 Air Louver 1 1051215901 Helicoid Tongue 2611218702 Left Axile Bush 10512037 Rear Case assy 22202363 Rubber Plug (Water Tray) 76712012...
  • Page 186 Super Free Match Service Manual Evaporator Assy 01002437 Wall Mounting Frame 01252032 Motor Press Plate 26112316 Fan Motor 15012098 Pipe Clamp 2611218801 Drainage hose 0523001405 Step Motor 1521300101 Crank 10582070 Display Board 30565110 Guide Louver 10512208 Axile Bush 10542036 Electric Box 20112108 Terminal Board 42011233...
  • Page 187 Super Free Match Service Manual 7.2.2 Duct type GFH(09)EA-K3DNA1A/I; GFH(12)EA-K3DNA1A/I Part list: GFH(09)EA-K3DNA1A/I for CN210N0010; GFH(12)EA-K3DNA1A/I for CN210N0020 GFH(09)EA-K3DNA1A/I GFH(12)EA-K3DNA1A/I Description Code Code Air outlet frame assy 01865216 01865216 Cover of air outlet 01265298 01265298 Water Tray Assy 01285332 01285332 Top Cover Board Assy 01265200099 01265325...
  • Page 188 Super Free Match Service Manual Terminal Board 420111041 420111041 Main Board 30226338 30226338 Capacitor 33010020 33010027 Electric Box Sub-Assy 01395100 01395100 Electric Box assy 01395980 01395983 Electric Box Cover 01424253 01424253 Cover Plate of the Fan 01265300 01265300 Bottom Cover Plate 01265299 01265299 Supporter...
  • Page 189 Super Free Match Service Manual GFH(18)EA-K3DNA1A/I Part list: GFH(18)EA-K3DNA1A/I for CN210N0030; GFH(18)EA-K3DNA1A/I Description Code Air outlet frame assy 01865217 Cover of air outlet 01265331 Water Tray Assy 01285333 Evaporator Assy 01024268 Lower Cover Plate Sub-Assy 01265328 Left Side Plate Assy 01315334 Plate of the Evaporator Sub-Assy 01495317...
  • Page 190 Super Free Match Service Manual Rear volute casing 26905206 Bottom Cover Plate 01265332 Transformer 43110233 Terminal Board 420111041 Main Board 30226338 Capacitor 33010027 Electric Box Sub-Assy 01395100 Electric Box assy 01395984 Electric Box Cover 01424253 Temperature Sensor 390001982G Ambient Temperature Sensor 39000206 Cover Plate of the Fan 01265333...
  • Page 191 Super Free Match Service Manual GFH(21)EA-K3DNA1A/I; GFH(24)EA-K3DNA1A/I Part list: GFH(21)EA-K3DNA1A/I for CN210N0040; GFH(24)EA-K3DNA1A/I for CN210N0050 GFH(21)EA-K3DNA1A/I Description GFH(24)EA-K3DNA1A/I Code Air outlet frame assy 01375224 Cover of air outlet 01265335 Water Tray Assy 01285334 Evaporator Assy 01024269 Lower Cover Plate Sub-Assy 01265339 Left Side Plate Assy '01315334...
  • Page 192 Super Free Match Service Manual Front volute casing 26905205 Rear volute casing 26905206 Bottom Cover Plate 01265337 Transformer 43110233 Terminal Board 420111041 Main Board 30226338 Capacitor 33010027 Electric Box Sub-Assy 01395100 Electric Box assy 01395985 Electric Box Cover 01424253 Cover Plate of the Fan 01265338 Temperature Sensor 390001982G...
  • Page 193 Super Free Match Service Manual 7.2.3 Cassette type GKH(12)BA-K3DNA2A/I; GKH(18)BA-K3DNA2A/I MAINTENANCE...
  • Page 194 Super Free Match Service Manual Part list: GKH(12)BA-K3DNA2A/I for CN510N0040; GKH(18)BA-K3DNA2A/I for CN510N0050 GKH(12)BA-K3DNA2A/I(Body ) GKH(18)BA-K3DNA2A/I(Body) Description Code Code Seat Board Sub-Assy 01222712 01222712 Front Side Plate 01302741 01302741 Right Baffle Assy 01362704 01362704 Water Pump 43130320 43130320 Pump Drainpipe 05232722 05232722 Body Installing Support...
  • Page 195 Super Free Match Service Manual GKH(12)BA-K3DNA1A/I; GKH(18)BA-K3DNA1A/I; GKH(24)BA-K3DNA1A/I Part list: GKH(12)BA-K3DNA1A/I for CN510N0010;GKH(18)BA-K3DNA1A/I for CN510N0020; GKH(24)BA-K3DNA1A/I for CN510N0030 GKH(12)BA-K3 GKH(18)BA-K3 GKH(24)BA-K3 Description DNA1A/I DNA1A/I DNA1A/I MAINTENANCE...
  • Page 196 Super Free Match Service Manual Code Code Code Tube Exit Plate Assy 01382717 01382717 01382715 Shell Assy 01432701 01432701 01432704 Body Installing Plate 01332701 01332701 01332701 Front Side Plate Assy 01302717 01302717 01302718 Left Side Plate Assy 01302740 01302740 01302715 Base Plate Assy 01222701 01222701...
  • Page 197 Super Free Match Service Manual 7.2.4 Floor ceiling type GTH(09)BA-K3DNA1A/I; GTH(12)BA-K3DNA1A/I Part list: GTH(09)BA-K3DNA1A/I for CN610N0010; GTH(12)BA-K3DNA1A/I for CN610N0020 GTH(09)BA-K3DNA1A/I GTH(12)BA-K3DNA1A/I Description Code Code Fixed Mount 26909426R 26909426R Louver Clamp 26112127 26112127 Guide Louver 10619403 10619403 Rotating Shaft 26909430 26909430 Front Connecting Plate 01349414P 01349414P...
  • Page 198 Super Free Match Service Manual Air Lead Plate sub-assy 02229418 02229418 Supporter 01805288 01805288 Mid-clapboard sub-assy 01249416 01249416 Front volute casing 26905205 26905205 Rear side plate assy 01319430 01319430 Centrifugal fan 10425200 10425200 Support 1 01809417 01809417 Right Side Plate Sub-Assy 01319429 01319429 Right Cover Plate...
  • Page 199 Super Free Match Service Manual GTH(18)BA-K3DNA1A/I Part list: GTH(18)BA-K3DNA1A/I for CN610N0030; GTH(18)BA-K3DNA1A/I Description Code Fixed Mount 26909426R Louver Clamp 26112127 Guide Louver 10619403 Rotating Shaft 26909430 Front Connecting Plate 01349414P Air Louver 10619404 Base Frame 26909448 MAINTENANCE...
  • Page 200 Super Free Match Service Manual Air Lead Plate sub-assy 02229418 Supporter 01805288 Mid-clapboard sub-assy 01249416 Front volute casing 26905205 Rear side plate assy 01319430 Centrifugal fan 10425200 Support 1 01809417 Axile Bush 10542704 Right Side Plate Sub-Assy 01319429 Right Cover Plate 26909444 Installation Supporting Frame 01809402...
  • Page 201 Super Free Match Service Manual GTH(24)BA-K3DNA1A/I Part list: GTH(24)BA-K3DNA1A/I for CN610N0040; GTH(24)BA-K3DNA1A/I Description Code Cable-Cross Loop 76510021 Room Sensor 39000191 Louver Clamp 26112127 Guide Louver 10619403 Front Connecting Plate 01349414P Rotating Shaft 26909430 Air Louver 10619404 Base Frame 26909448 MAINTENANCE...
  • Page 202 Super Free Match Service Manual Induced air plate subassembly 02229418 Supporter 01805288 Mid-clapboard sub-assy 01249416 Front volute casing 26905205 Rear side plate assy 01319430 Centrifugal fan 10425200 Supporter 01809417 Support Of Motor Bearing 01792408 Axile Bush 10542704 Right Side Plate Sub-Assy 01319429 Right Cover Plate 26909444...
  • Page 203 Super Free Match Service Manual 7.2.5 Console type GEH(09)AA-K3DNA1C/I; GEH(12)AA-K3DNA1C/I; GEH(18)AA-K3DNA1C/I MAINTENANCE...
  • Page 204 Super Free Match Service Manual Part list: GEH(09)AA-K3DNA1C/I for CV010N01500; GEH(12)AA-K3DNA1C/I for CV010N01600; GEH(18)AA-K3DNA1C/I for CV010N01700 GEH(09)AA-K3 GEH(12)AA-K3 GEH(18)AA-K3 Description DNA1B/I DNA1B/I DNA1B/I Code Code Code Front Panel Assy 20012756 20012756 20012756 Filter Sub-Assy 11122139 11122139 11122139 Front Case Assy 20012601 20012601 20012601...
  • Page 205: Bu Module

    Super Free Match Service Manual 7.3 BU Module FXB3A-K; FXB5A-K Part list: FXB3A-K FXB5A-K Description Code Code Coping 01264100017P 01264100017P Electric Component Mounting Plate assy 01324100023 01324100023 Sponge 12204100052 12204100052 Tube Clip 021400051 021400051 Tube Clip 021400052 021400052 Electrical Equipment Plate 01424731P 01424731P Electric Expand Valve Fitting...
  • Page 206 Super Free Match Service Manual Cable Cross Loop 76510021 76510021 Retaining Plate (Water Level Switch) 01844100017P 01844100017P Sponge 12204100057 12204100057 Sponge 12204100055 12204100055 Retaining Plate (Water Level Switch) 01844100019P 01844100019P Retaining Plate (Water Level Switch) 01844100018P 01844100018P Sponge 12204100053 12204100053 Sponge 12204100054 12204100054...
  • Page 207 JF00301896...

Table of Contents