(7) Temperature variation range
With the narrow range, the temperature features a small amount of variation for great comfort, but the
fan and water valve will operate more frequently causing loss of service life. Whereas, the wide range does
good to duration of the fan and water valve with a large amount of temperature variation and low frequency
operation. The medium range ("2") is adopted by default which is advisable. The three ranges above are
available.
As shown in the Figure 13, on the parameter setting page, press
number to 07.
(UP) or
(8) Cooling temperature set in the energy saving mode
It is available when energy saving function is enabled. The cooling temperature is limited between 16°C
and 30°C (61°F~86°F).
As shown in the Figure 14, on the parameter setting page, press
number to 08.
(UP) or
the temperature unit is Celsius, the adjustment range is 16°C~30°C with a precision of 0.5°C. If the
temperature unit is Fahrenheit, the adjustment range is 61°F~86°F with a precision of 1°F.
(DOWN) is provided to a switch between "1", "2" and "3" (the three ranges).
Figure 13
(DOWN) is provided to allow a rise or drop on the temperature. If
Figure 14
20
Vertical Exposed Fan Coil Unit
(MODE) to switch the option
(MODE) to switch the option