Safety
Introduction
Selecting the Concentrate Source—F5
1. Enter the calibration/setup mode. Refer to:
"Entering the Calibration/Setup Mode" on page
2. Navigate to
(F5 parameter).
3. Press the
(SELECT button) to edit the parameter.
4. Use the
or
foam tank pairing:
• Select
(AA) when you source from a single tank that
supplies A foam or when you source from 2 tanks that supply A
foam. The proportioning value for this setting is between 0.1% to
1.0% for both tanks.
• Select
(Ab) when you source from 2 tanks that supply
A foam from one tank (tank A) and B foam from the other tank (tank
B). The proportioning value for this setting is between 0.1% to 1.0%
for the A foam tank and 1.0%, 3.0% and, 6.0% from the B foam
tank.
• Select
(bb) when you source from a single tank that
supplies B foam or when you source from 2 tanks that supply B
foam. The proportioning value for this setting is 1.0%, 3.0% or,
6.0% for both tanks.
• Select
(AF) when you source from a 2 tanks that
supply combination A/B foam. The proportioning value for this
setting is between 0.1% to 1.0%, 3.0% or, 6.0% for both tanks.
5. Press the
(SELECT button) to return to the
parameter).
6. Press the
(FOAM button) to save the value and exit the
Product Overview
46.
(up or down button) to display the desired
Installation
Operation
calibration and setup mode.
Simulating Water Flow—F6
Use this mode to test and verify the foam system operation. This
function is available for the AQUIS 1.5 with digital head, AQUIS 3.0 and
AQUIS 6.0.
1. Enter the calibration/setup mode. Refer to:
"Entering the Calibration/Setup Mode" on page
2. Navigate to
3. Press the
4. Use the
simulated flow rate from the following choices:
AQUIS 1.5
AQUIS 3.0
AQUIS 6.0
5. Press the
6. Position the inject/bypass valve to bypass. Refer to:
"Operating the Inject/Bypass Valve" on page
7.
Press the
Note: Make sure that the output has equalized for up to 3 minutes before
you collect the concentrate.
8. Collect the concentrate that flows from the bypass hose for 1 minute.
(F5
9. Press the
10. Measure the volume of concentrate.
11. Use the following chart to determine your flow rate.
|
49
64
Maintenance
Troubleshooting
(F6 parameter).
(SELECT button) to edit the parameter.
or
(up or down button) to display the desired
Flow Rate Settings
Flow Rate Settings
0
50
100
0
50
100
0
100
200
(SELECT button) to save the value.
(FOAM button) to start the pump.
(FOAM button) to stop the pump.
46.
200
200
300
57.