Points Definition; Bacnet Server; Description - HMS Networks Intesis IN701-KNX Series User Manual

Intesis protocol translator with knx, serial, and ip support
Table of Contents

Advertisement

Points Definition

12.4. Points Definition
Every point defined in the Intesis gateway has the following BACnet features associated with it:
Feature
BACnet Device
BACnet device to which the point belongs (a list of 256
BACnet devices can be defined in the Intesis gateway).
For every BACnet device defined, a virtual signal is
created automatically in the gateway to report the
communication status with the BACnet device. Like the
rest of the points, this signal is also available from the
KNX interface.
BACnet object type
• AI: Analog Input
• AO: Analog Output
• AV: Analog Value
• DI: Digital Input
• DO: Digital Output
• DV: Digital Value
• MI: Multistate Input
• MO: Multistate Output
• MV: Multistate Value
• LOOP: Loop
• ACUM: Accumulator
BACnet object instance
BACnet object instance for the point on the external
BACnet device.

12.5. BACnet Server

12.6. Description

NOTICE
When the Intesis gateway acts as a server device, it is classified under the device profile of a BACnet
Advanced Application Controller (B-AAC). For further details, check out the product website for the
BACnet client PIC statements.
Using the configuration tool, you can configure the object type associated with the signal on the other protocol.
USER MANUAL Version 1.0
Description
IMPORTANT
Please read the documentation of
the BACnet devices you're willing to
integrate to know their object types.
IMPORTANT
Please read the documentation of
the BACnet devices you're willing to
integrate to know their object types.
IN701-KNX Series
Page 21 of 44