EXAMPLE OF RENEWAL PERFORMANCE
Yield during dehumidification in renewal mode, with a flow rate
of 240 m
/h, with a unit supplied with water at a temperature of
3
15 °C, with outdoor air delivery at 35° and a R.H. of 50% and later
delivered back into the room at 26° and R.H. of 44.8%.
Air key
Legenda aria
Outdoor Air Intake
Ae1
Ingresso aria esterna
Post Recovery Unit Outdoor Air
Ae2
Aria Esterna Post Recuperatore
Pre-Treatment Post-Coil
C
Post Batteria Pre-Trattamento
Evaporator Post-Coil
D
Post Batteria Evaporante
Room Air Delivery
E
Immissione Aria ambiente
Air ow diagram - Schema Flusso Aria
Ae1
Psychometric diagram - Diagramma Psicrometrico
0
5
1
2
Ae2
C
D
10
15
Wet bulb temperature - (°C)
Temperatura Bulbo Umido - (°C)
ESEMPIO PRESTAZIONE RINNOVO
Resa in deumidificazione in modalità rinnovo con portata di
240 m
/h, unità alimentata con acqua a 15 °C, Ingresso Aria
3
Esterna a 35° e 50% U.R. e successiva Immissione in ambiente
a 26° e 44.8% U.R.