3 START-UP AND TESTING - AVVIAMENTO E COLLAUDO
3.1 HYDRAULIC CIRCUIT ADJUSTING / TARATURA CIRCUITO IDRAULICO
The dehumidifier must be tested together with the panel system in
summer operating mode; the main check which must be performed
regards the cooling water flow rate which must be approximately
360 l/h when the water temperature is approximately 15 °C. By
using lower temperatures, water flow rates will be inferior too.
Very low flow rate values can cause malfunctioning
in UC 360 V1 unit and they can activate relevant
alarms. In this case the unit stops working and shall
be restarted manually.
Do not use the dehumidifier without the chilled water:
this may damage the machine itself!
Il collaudo del deumidificatore andrebbe effettuato
contestualmente a quello dell'impianto a pannelli in
funzionamento estivo; la principale verifica da effettuare
riguarda la portata dell'acqua di raffreddamento che dovrebbe
essere di circa 360 l/h quando la temperatura dell'acqua è di
circa 15 °C. Con temperature dell'acqua più basse, anche le
portate devono essere inferiori.
6 l/min
(360 l/h)
Portate insufficienti causano malfunzionamenti
all'unità UC 360 V1 e l'attivazione di allarmi con
blocco macchina a riarmo manuale.
Non utilizzare il deumidificatore senza l'acqua
refrigerata: questo può portare al danneggiamento
della macchina stessa!