RDZ UC 360 V1 Installation & Technical Manual page 66

Air handling units
Table of Contents

Advertisement

EXAMPLE OF RECIRCULATION PERFORMANCE
Yield during dehumidification in recirculation mode, with a flow
rate of 360 m
/h, with a unit supplied with water at a temperature
3
of 15 °C, with room delivery air at 26° and a R.H. of 65% and later
delivered back into the room at 26° and R.H. of 47.4%.
Air key
Legenda aria
Room air intake
Ai
Ripresa aria ambiente
Pre-treatment post-coil
C
Post batteria Pre-Trattamento
Evaporator post-coil
D
Post batteria Evaporante
Room air delivery
E
Immissione aria ambiente
Air ow diagram - Schema Flusso Aria
Ai
Psychometric diagram - Diagramma Psicrometrico
0
5
1
2
C
C
D
10
15
Wet bulb temperature - (°C)
Temperatura Bulbo Umido - (°C)
ESEMPIO PRESTAZIONE RICIRCOLO
Resa in deumidificazione in modalità ricircolo con portata di 360
m
/h, unità alimentata con acqua a 15 °C, Ripresa Aria ambiente
3
a 26° e 65% U.R. e successiva re-immissione in ambiente a 26°
e 47.4% U.R.
Parts key
Legenda componenti
Recovery unit
1
Recuperatore
Pre-treatment coil
2
Batteria Pre-Trattamento
Evaporator coil
3
Batteria Evaporante
Condenser coil
4
Batteria Condensante
Delivery fan
5
Ventilatore Immissione
3
4
5
D
Ai
E
20
25
66
E
30
35
20
15
10
5
40