AC Infinity CLOUDLINE PRO S Series User Manual page 52

Mixed flow inline fan systems
Table of Contents

Advertisement

PROGRAMMING
T-SERIES
TRANSITION HUMIDITY SETTING
Adjusts how gradually your device will shift between
levels when triggered ON by the AUTO Mode's
humidity trigger. This will determine how much the
probe humidity needs to increase to step up to the
next level setting.
The higher the transition setting is, the wider the
humidity gap is between levels. The lower the
transition setting is, the smaller the humidity gap is
between levels. If this figure is set to zero, your device
will jump to your maximum level when triggered ON.
Press the up or down button to set a transition
threshold between 0% and 10%. When the sensor
humidity first reaches or exceeds the high humidity
trigger point, the level will increase by one (exiting
OFF Mode). Each time the threshold level is crossed,
the level will ramp up by one until it reaches the level
set in ON Mode.
EXAMPLE
In this example, your high humidity trigger is set at
70%, the OFF Mode level is 0, and the ON Mode
level is 6. If the transition threshold is set to 0%,
then once the sensor humidity reaches or exceeds
70% then the devices will trigger to run at level 7.
However, if the transition threshold is set to 2%, then
the fan will trigger to run at level 1 when it reaches
or exceeds 70%. It will then step up to level 2 when
reaching or exceeding 72%, level 3 at 74%, and level
4 at 76%, etc. From 80% on, it will run at level 6, the
level set in ON Mode.
52

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents