Installing Plastic Fibers QS18V..6FP
Follow these steps to install the plastic fibers.
1. Slide the fiber gripper up to unlock it (A).
2. If using 0.25 mm or 0.5 mm core fibers, slide the plastic fiber adapters onto the fibers, flush with the fiber ends.
3. Carefully insert the prepared plastic fiber ends into the ports (B) as far as possible without applying extra force.
4. Slide the fiber gripper down to lock the fibers in place (C).
Installing Glass Fibers QS18V..6F
Follow these steps to install the glass fibers.
1. Slide the supplied o-ring on the sensor end of the fibers, as shown.
2. Press the fiber ends firmly into the ports located on the front of the sensor.
3. Slide the supplied u-shaped retaining clip into the slot in the sensor's barrel until the clip snaps into place.
Specifications
Supply Voltage
10 V dc to 30 V dc (10% maximum ripple) at less than 25 mA, exclusive of
load
Protected against reverse polarity and transient voltages
Light Source
Glass Fiber Optic, Opposed and Diffuse mode models: Infrared, 940 nm
Plastic Fiber Optic, Retroreflective, Convergent models: Visible red, 660 nm
Fixed-Field and DVS models: Visible red, 630 nm
Adjustments
Glass Fiber Optic, Plastic Fiber Optic, Convergent, Diffuse, and
Retroreflective mode models (only): Single-turn sensitivity (Gain) adjustment
potentiometer
Indicators
2 LED indicators on sensor top
Green: Power on
Amber: Light sensed
Amber flashing: Marginal excess gain (1 to 1.5 times excess gain)
4
A
C
B
Figure 2. Installing Plastic Fibers
Figure 3. Installing Glass Fibers
www.bannerengineering.com - Tel: + 1 888 373 6767
Adapter
Adapter Installation
Retaining Clip
O-rings
Repeatability
Opposed Mode: 100 microseconds
DVS, DL and FF Modes: 90 microseconds
All Other Modes: 150 microseconds
Output Configuration
Solid-state complementary (SPDT): NPN or PNP (current sinking or
sourcing), depending on model;
Rating: 100 mA maximum each output at 25 °C
DVS, DL and FF Modes ON-state Saturation Voltage: less than 1.5 V at 10
mA; less than 3 V at 100 mA
All Other Modes: ON-state Saturation Voltage: less than 1 V at 10 mA; less
than 1.5 V at 100 mA
Protected against false pulse on power-up and continuous overload or short
circuit of outputs
Output Response
Opposed Mode: 750 microseconds ON; 375 microseconds OFF
DVS, FF and DL Modes: 850 microseconds ON/OFF
All Other Modes: 600 microseconds ON/OFF
100 millisecond delay on power-up; outputs do not conduct during this time
®