Programmable Inputs, P Channels; Programmable Input 1 - DAAB EP104 Instruction Manual

Hide thumbs Also See for EP104:
Table of Contents

Advertisement

• Programmable inputs, P channels

Programmable input 1

No.
Name
P100
Channels in programmable input 1
0
Disabled
1
Enabled
P160
Control function
0
Disabled
1
Open
2
Close
3
Stop
4
Open/close
5
Open/stop/close
P161 Type of control signal when activated
S
1
Pulse (hold-to-run mode not possible)
2
Signal for as long as the input is activated
P162
Half operation
1
Motor 1
2
Motor 2
3
Motors 1 and 2
P163
Limited opening
0
Disabled
1
Opening according to set time in channel C412/C414 or number of degrees in L116/L126 if encoder
is used.
P170
Motor lock
0
Disabled
1
The barrier cannot be operated without a signal at programmable input 1. If the signal disappears the
barrier is stopped.
P175
Opening via input after activation during set time,
input will not open the barrier until it has been
activated for the set time.
P180
Keep opened
0
Disabled
1
Automatic closing disabled after the input is activated, reset by another control signal
2
Automatic closing disabled by a constant signal
P190
Interlock opening
0
Disabled
1
Opens the local door if P160 is set to open, and passes the signal on to the remote door
P196
Blocking disabled for local and remote doors. Works
only with a constant signal.
0
Disabled
1
Active
P198
Automatic closing disabled for remote door Only
works if there is a constant signal
0
Disabled
1
Active
46
INSTRUCTION MANUAL DAAB AUTOMATIC CONTROLL UNIT EP104 4.08
Range
Factory Setting Ref.
0 - 1
1
0-5
1
1 - 2
1
1 - 3
3
0 - 1
0
0 - 1
0
0.0-9.9 seconds
0.0
0 - 2
2
0 - 1
0
0 - 1
0
0 - 1
0
Instruction manual edition 1 for EP104 version 4.08
page
31
31
31
31
31
31
31
31
31

Advertisement

Table of Contents
loading

Table of Contents