Commissioning Of Drive Unit 2 - DAAB EP104 Instruction Manual

Hide thumbs Also See for EP104:
Table of Contents

Advertisement

INSTRUCTION MANUAL DAAB AUTOMATIC CONTROLL UNIT EP104 4.08

• Commissioning of drive unit 2

Preparation: Set C999 to 2. Open gate leaf 1 and set L001 to 0 to maintain the gate leaf in open position. Set C033 to 5,
Service mode.
Direction of movement: Set L002 to 4, hold-to-run without limit switches. Check that the drive arm mounting is moving in
the right direction while pressing OPEN or CLOSE button on the controll board. If the direction of movement is wrong, see
section "Connections" in the "Instruction Manual EP104".
Open and closed position: Engage gate leaf of drive unit 2 and set the positions for open and closed. After this is done
L002 should be set to 1, Encoder.
L110=1, Drive unit 1 Left position
Motor protection: Read out motor current in C261 under operation and apply appropriate values in C262 och C263.
Opening/Closing
Current(A)
150%
C262/C263
C261, Read out current
(50%)
C221
Current(A)
Opening/Closing
150%
C262/C263
(50%)
C221
Load guard: Set C999 to 3. A swing gate application usually does not require personal protection, if so C240 is set to
0.00. Set C033 to 3, impulse, to activate the load guard. Make sure that the settings of the C242 and C243 is low enough to
prevent material damage, but at the same time that it is guaranteed to open due to weather, wind and mechanical changes.
Opening/Closing
Power(kW)
C241, Power read out
C242/C243
C212, Load guard start
Safety edges: Check the safety edges on gate leaf 2 by pressing the safety edges during movement. Please note that the
safety function in opening direction is switched off in C141. If the safety edges are activated during closing movement the
gate should reverse to fully opened position, while in opening movement it should reverse to closed position during the time
in C494. A flashing indication at SE.C2 or SE.O2 means that the safety edge was activated but no longer is.
Completion: Set L001 to 1, Encoder and fine-tune both gate leaf's in closed position using L113 and L123.
Use channel C999 set to 1 to look for changed channels and enter all changed channels in the "Instruction Manual".
Instruction manual edition 1 for EP104 version 4.08
150%
E202
C262/C263
(50%)
Time
C221, Motor protection delay
150%
C261, Read out current
C262/C263
E207
(50%)
Time
C221, Motor protection delay
C242/C243
Reversing
-0,30kW
Time
C211, Load guard delay
L123, Closed position
Current(A)
Opening/Closing
Opening/Closing
Current(A)
C261, Read out current
Opening/Closing
Power(kW)
C241, Power read out
C212
L120=2; Drive unit 2 Right position
L122, Open position
C261, Read out current
Time
Time
Time
21