9
HARMONICS
Setting of up to which maximum harmonic the calculation shall be done.
Note: the more harmonics are calculated, the slower the display of the harmonics is
updated!
10 C-FAULT( + )
Here the upwards deviation from the capacitor's nominal value can be determined.
In case this value is reached, an error message is displayed.
(available in operation mode 6 only)
11 C-FAULT (-)
Here the downwards deviation from the capacitor's nominal value can be
determined. In case this value is reached, an error message is displayed.
(available in operation mode 6 only)
12 TEST ATTEMPTS
A C-error message is displayed only after these given numbers of consecutive
measurements have indicated an error of the capacitor output.
(available in operation mode 6 only)
13 SYMMETRY
Dynamic part of the compensation in the hybrid mode which is not transferred into
static steps (application: fast switch off)
Only available in the Hybrid mode: operation mode 7...14
14 PROTOCOL Com 1
- [ None ]
- [ MODBUS KTR ]
- [ MODBUS RTU ]
Depending on the selection of the protocol, the following configuration menu is offered:
15 BAUDRATE (symbol rate) Com1
possible transfer rates are:
9600/ 19200/ 38400/ 57600/ 115200/ 128000/ 250000/ 256000 Baud
each with parity NONE, ODD or EVEN
16 BUS-ADDRESS Com1

=== EXPERT-MODE ===

[NO]
(NO /3. - 7. ... 3. - 31.)
[40]%
(10...100%)
[40]%
( 10...100 %)
[6]
( 2...9)
[MODBUS-RTU]
- Interface switched off
- MODBUS- with interface monitoring
- MODBUS-protocol (default)
[9600/NONE]
[1]
(1... 255)
- 24 -