Operation Diagram - janitza Prophi 15T-III Manual

Power factor controller
Table of Contents

Advertisement

=MANUAL-MODE=
1 MAN. OPERATION L1
cos j
L1
[ STOPP ]
1 MAN. OPERATION L2
cos j
L2
[ STOPP ]
1 MAN. OPERATION L3
cos j
L3
[ STOPP ]
2 STEP STATE
L1
OUTPUT C1 [AUTO]
C2...C14
2 STEP STATE
L3
OUTPUT C15 [AUTO]
After 4 min. without pressing
any button, automatic change
to auto-mode
Settings shown with grey background
colour are active only in case
of certain other settings.
If not needed they are not displayed.
Operating diagram (Brief programming)
Power Factor Controller Prophi 15T-III
== SERVICE ==
1 min/max VOLTAGE
*
L1-N
230 / 235 V
L1-N
230 / 235 V
L1-N
230 / 235 V
2
max CURRENT
L1
123 A
L2
239 A
L3
167 A
3 max REACTIVE PWR
L1
88 kvar
L2
88 kvar
L3
88 kvar
4 max ACTIVE PWR
L1
88 kW
L2
88 kW
L3
88 kW
5 max APPARENT PWR
L1
88 kVA
L2
88 kVA
L3
88 kVA
6 max TEMPERATURE
35 °C
7 max THD-V THD - I
L1
V 1.0% I 2.0%
L2
V 1.0% I 2.0%
L3
V 1.0% I 2.0%
8
MAX. VALUES
RESET [ NO ]
9 ERROR MEMORY
.....ERROR TEXT.....
.....DATE / TIME ....
10
ERROR MEMORY
RESET [ NO ]
BACK TO 1
- 40 -
===== EXPERT-MODE 1 =====
PASSWORD ????
0 * * *
(6343)
1 BASIC SETTINGS
[ NO ]
2
SWITCH.POWER
max [ 160 ] kvar
3 SWITCH.TRIGGER
[ 66 ] % IND
66 % CAP
4 SWITCH.TRIGGER
66 % IND
[ 66 ] % CAP
5 OPERATING LOCK
[ NO ]
6
CONTROL
[ MEAN VALUE ]
7 OUTPUT 1st STEP
[ 0...255] kvar
8 DISPLAY
[ COS PHI ]
9
HARMONICS
[ 3. - 7. ]
10
C-FAULT ( + )
[ 40 ] %
11
C-FAULT ( - )
[ 40 ] %
12 TEST ATTEMPTS
[ 6 ]
Prophi
15T-III
®
13 SYMMETRY
[ 0 ] %
14 PROTOCOL COM1
[ MODBUS RTU ]
15 BAUD RATE COM1
[ 9600/ NONE ]
16 BUS ADRESS COM1
[ 1 ]
BACK TO 1
41