janitza Prophi 15T-III Manual page 24

Power factor controller
Table of Contents

Advertisement

Prophi
15T-III
®
Section 10:
EXPERT-MODE 1 and 2
The expert modes are meant for the adjustment of values which normally should not be
changed. As a protection these levels have access codes:
PASSWORD:
ExpertMode 1: "6343"
ExpertMode 2: "2244"
10.1 EXPERT-MODE 1 (Code: 6343)
1 BASIC SETTINGS NEW
Storage of the present programming as a new basic setting (usually performed
by the PFC-system manufacturer).
Caution: All original values will be overwritten!
2 SWITCHING POWER max
This factor specifies the maximum power which may be switched in one
switching step. It can be used to control the intelligent control system,
which switches several stages as a function of the power-factor requirement.
3 SWITCHING TRIGGER
Threshold for switching on of the next stage. (IND. direction)
4 SWITCHING TRIGGER
Threshold for switching on of the next stage. (CAP. direction)
5 OPERATING LOCK
24 H means,that the lock will be automatically after 24 hours.
6 CONTROL
Only at single-phase measuring!
Selection whether the control during single-phase measuring should be done
according to the mean or the maximum value of the missing reactive power (of
the 3 phases)
7 POWER 1st stage
Here the range for the input of the 1st stage power can be set to [0...2550]
8 DISPLAY
Switch over between COS Phi or TAN Phi in the display
24
[NO]
( NO/YES)
[100] kvar
(multiple of smallest step)
[66]% IND
(30...100%)
[66]% CAP
(30...100%)
[NO]
(NO / YES / 24H)
[MEAN VALUE]
(Mean /Maximum value)
[0...255]
(0...2550)
j
[cos
]
(cos / tan
- 23 -
EXPERT-MODE
PASSWORD ????
0***
j
)