===== EXPERT-MODE 2 =====
PASSWORD ????
0 * * *
(2244)
1 DISPLAY / ALARM
[ YES ]
Release [YES] or
blocking [NO] of
following reports
or alarms:
MEAS.VOLTAGE ?
OVERVOLTAGE
OVER-COMPENSATED
UNDERCOMPENSATD
HARMONICS !
OVERTEMPERATURE
OVERCURRENT
UNDERVOLTAGE
UNDERCURRENT
ERROR COM 1
ERROR COM 2
BUS-SWITCH OFF
BUS-STOP
BUS-SWITCH ON
SYSTEMCURRENT < ?
BUS-ERROR-EXT.
C-DEFECT
SYSTEMCURRENT > 0
SYSTEM-OVERLOAD
EXTERNAL ERROR
C-DEFECT-OFF
UNDERVOLTAGE
24VDC (Aux.voltage)
2
ALARMRELAY
DELAY
[ 10 ] min
3
UNDERVOLTAGE
LIMITING VALUE
200 V [ 50 ]%
42
4 OVERVOLTAGE
LIMITING VALUE
460 V
[ 115 ] %
5 THD-MEAN VALUE
MEAS.CYCLES
[ 3 ]
6 UNDERVOLTAGE
24 VDC
[ < 12V ]
BACK TO 1
- 41 -
= OSCI-MODE =
L1
L2
L3
BACK TO 1
=DISPLAY EDITOR=
1 DISPLAY LINE 1
*
1 [ REACTIVE PWR
S
]
2 ACTIVE PWR
S
3 APPARENT PWR S
2 DISPLAY LINE 2
*
1 [ REACTIVE PWR
S
]
2 ACTIVE PWR
S
3 APPARENT PWR S
3 DISPLAY LINE 3
*
1 [ REACTIVE PWR
S
]
2 ACTIVE PWR
S
3 APPARENT PWR S
4 BASIC SETTING
[ NO ]
BACK TO 1