Annex 1:
Table of control series
Control serie
No.
1
1 : 1 : 1 : 1 : 1 .....
2
1 : 2 : 2 : 2 : 2 .....
3
1 : 2 : 3 : 3 : 3 .....
4
1 : 2 : 3 : 4 : 4 .....
5
1 : 2 : 4 : 4 : 4 .....
6
1 : 2 : 3 : 6 : 6 .....
7
1 : 2 : 4 : 8 : 8 .....
8
1 : 1 : 2 : 2 : 2 .....
9
1 : 1 : 2 : 3 : 3 .....
10
1 : 1 : 2 : 3 : 6 .....
11
1 : 1 : 2 : 4 : 4 .....
1 : 1 : 2 : 4 : 8 .....
12
13
1 : 1 : 1 : 2 : 2 .....
14
1 : 1 : 1 : 2 : 3 .....
1 : 1 : 1 : 2 : 4 .....
15
16
1 : 1 : 1 : 2 : 5 .....
17
1 : 1 : 1 : 1 : 2 .....
18
1 : 1 : 1 : 1 : 3 .....
19
1 : 1 : 1 : 1 : 4 .....
20
1 : 1 : 1 : 1 : 5 .....
"ED"
Control-series editor
Control series editor: Programming of step values up to 30
The control series editor enables easy creation of own control series in case the required
control series is not available.
In "PROGRAM-MODE" the last control series - control series ED - has to be selected and
confirmed by ENTER. This adds an additional menu point to the main menu -> control
series editor. It can be accessed via button „operation mode".
In the control series editor all stages can be set consecutively to the desired value with the
selection buttons é /ê. Pressing ENTER leads to the next stage.
In the control series editor the particular stages can be programmed up to a value of 30
(!). The values >9 are displayed as follows:
10=A, 11= B, 12=C, 13=D, 14=E, 15=F, 16=G
Attention: All control series can be edited (even downwards). Whether an edited control
series "makes sense" is the decision of the customer.
Maximum number of stages can be limited by a programmed ENDSTOP.
By pressing button "Operation mode" the editor is left.
....
30=U
- 32 -
Prophi
15T-III
®
Loop connection
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible
possible