janitza Prophi 15T-III Manual page 21

Power factor controller
Table of Contents

Advertisement

=== Actual assignment of outputs ===
Example:
CONTROL-MODE 2 (MIXED-MODE)
set in END STOP to:
4 stages with 3 single- phase capacitors each and
3 stages with 1 three-phase capacitor each
L1 (R)
L2 (S)
L3 (T)
N
PE
Monitoring
24VDC
Transistor-
output 1-5
P1 1
2
3
4
5
Aux. voltage
24VDC
In case of the setting the controller will automatically assign the capacitors according to
the wiring diagram.
This output assignment can always be called up in help-mode AUTO-MODE/ HELP/ page
7...9 and is displayed in the example as follows:
HELP-MODE p. 7/9
OUTPUT ASSIGNMENT
Thy T01 -> L1 -> C1.1
Thy T02 -> L1 -> C2.1
Thy T03 -> L1 -> C3.1
Thy T04 -> L1 -> C4.1
S
S
Thy T05 ->
-> C1
Output assignment
Transistor-
Transistor-
output 6-10
output 11-15
P2 6
7
8
9 10
P3 11 12 13 14 15
HELP-MODE p. 8/9
OUTPUT ASSIGNMENT
Thy T06 -> L2 -> C1.2
Thy T07 -> L2 -> C2.2
Thy T08 -> L2 -> C3.2
Thy T09 -> L2 -> C4.2
S
Thy T10 ->
-> C2
- 20 -
4 x3 Single phase steps
T1
T6
T11
(T2)
(T7)
(T12)
(T3)
(T8)
(T13)
(T4)
(T9)
(T14)
C1.1
C1.2
C1.3
(C2.1)
(C2.2)
(C2.3)
(C3.1)
(C3.2)
(C3.3)
(C4.1)
(C4.2)
(C4.3)
e.g. TSM-LC-I
HELP-MODE p. 9/9
OUTPUT ASSIGNMENT
Thy T11 -> L3 -> C1.3
Thy T12 -> L3 -> C2.3
Thy T13 -> L3 -> C3.3
Thy T14 -> L3 -> C4.3
S
Thy T15 ->
Prophi
15T-III
®
3 x Three phase steps
T5
(T10)
(T15)
C1S
( C2S )
( C3S )
TSM-LC-N
S
S
-> C3
21