Section 8: MANUAL OPERATION
Manual operation is designed for maintenance and service
purpose. Menu "MANUAL-MODE" consists of the following sub-
windows:
1
MANUAL CONTROL [STOP] L1
In
manual
connected /disconnected according to the control
series and switching time irrespective of the prevailing
power-line-conditions.
Starting position is STOP (no stages connected).
CONNECTION or DISCONNECTION is done by pressing
the buttons é resp. ê
This manual operation is executed consecutevely for
particular phases L1-L3 resp. S.
The operation status and the power power factor of the
actual phase are permanently shown in the display.
2
STEP STATE
C1 - [AUTO]
In special cases, all controller outputs (C1- C15) may be
permanently defined (continued switching via ENTER) for
the following states:
AUTO: Automatic (normal) operation
The relevant output is marked by a capacitor symbol.
FIXED: The output is continuously connected, e.g. for
fixed PFC. The output is marked by an underlined
capacitor symbol.
OFF: The output is continuously disconnected, e.g. for
temporarily disconnecting of a defective capacitor. The
capacitor symbol for this output is faded out. "MINUS"
sign appears.
The active stage is blinking. The required status is set via
é / ê. By pressing ENTER, the user saves this step and
moves to the next stage.
The programmed status for the outputs also remains
visible on the display in automatic operation.
22
( L1...L3)
operation,
capacitor
(FIXED/ AUTO/ OFF)
- 21 -
steps
can
be
1 MAN.OPERATION
L1
[SWITCH ON ]
L1
1 MAN.OPERATION
L1
[SWITCH OFF]
L1
2 MAN.OPERATION
OUTPUT C1 [AUTO]
L1
2 STEP STATE
OUTPUT C1 [FIXED]
L1
2 STEP STATE
OUTPUT C1 [OFF]
L1
MANUAL-MODE
L1
j
cos
0.983 IND
1 2 3 4 5
MANUAL-MODE
L1
j
cos
0.983 IND
1 2 3 4 5
MANUAL-MODE
L1
1 2 3 4 5
MANUAL-MODE
L1
1 2 3 4 5
MANUAL-MODE
L1
1 2 3 4 5