Application Hybrid-Mode - janitza Prophi 15T-III Manual

Power factor controller
Table of Contents

Advertisement

Prophi
15T-III
®

12.2. Application HYBRID-MODE :

A mixed dynamical compensation system implements economically the advantages of a
dynamic fast network. (Fast changing loads are compensated dynamically and basic
loads / slowly changing loads are compensated conventionally)
For designing a mixed-dynamical compensation system a special controller was
developed. The Prophi-12TR supports up to 12 transistor-outputs (for triggering thyristor
modules) and additional 12 relay-outputs for standard capacitor contactors.
In systems where more than 12 outputs are required respectively where the dynamic part
is to be compensated for single phases, following application can be used. Here the
dynamic part is compensated by the Prophi 15T-III (single or three phase) and the base
load is compensated conventionally by the Prophi-12RS.
Programmierung und Anschluß
Prophi 15T-III
(for dynamical steps)
Menu: PROGRAMMING
2 CONTROL-MODE: 7...14
Prophi 15T-III
30
Adress: [1]
LAN-cablel (CAT5/CAT6)
Prophi 12RS
- 29 -
Prophi 15T-III and Prophi 12RS
up to 2 Prophi-12RS
(für conventional steps)
Menu: INTERFACE
Protocol: [Slave Hybrid]
Baudrate: [38400/NONE]
Adress: [2]
LAN-cable (CAT5/CAT6)
Adapter
CV-1xRJ45-BR6000
Prophi 12RS

Advertisement

Table of Contents
loading

Table of Contents