Startup Activities Of The Tim 3 And Tim 4 - Siemens SIMATIC NET SINAUT ST7 System Manual

Station control system
Table of Contents

Advertisement

5.7.3

Startup activities of the TIM 3 and TIM 4

Introduction
During startup, the LEDs on the front panel of the TIM 3 / TIM 4 have a different significance
than during normal operation. They are optical indicators of the various startup phases and
provide detailed information about any errors detected during startup.
LED displays during startup
The following table summarizes the startup phases.
Table 5-46
LED activity on the TIM 3 / TIM 4 during the various startup phases
Phase
Activity
1
Power ON
2
RAM test
3
Service mode
4
Software startup
5
Startup completed
Table 5-47
LED activity during software startup (startup phase 4)
Phase
4.1
Starting the RMOS operating system
4.2
Starting the TIM firmware
4.3
Start normal startup
Start default startup
4.4
Startup of the TIM as CP in the S7-300 rack
Startup of the TIM on MPI (TIM 4 only)
4.5
Normal startup with parameters
Normal startup without parameters
Default startup
The LEDs whose activity is not shown in brackets ( ), provide the actual information on the
current startup phase.
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
Explanation
All LEDs light up at the same time.
Starting with LED 6 (DCF77), the LEDs go off one after the other at intervals of
approximately 10 seconds. If an error is detected during the RAM test, LED 1 (SF
group error)
remains lit at the end. If everything is OK, the TIM changes to phase 3.
After all the LEDs have gone off, all LEDs light up again for 5 seconds. During this time,
the user can force a default startup (see below) using the reset button. Otherwise, the
TIM changes to phase 4.
All the LEDs go off again and then light up again one after the other starting with LED 2
(TXD). At this stage of startup, the individual steps of the software startup are signaled
by the LEDs. The LEDs are either lit continuously or flash. The following table lists the
exact meaning of the individual LEDs when lit continuously or flashing during this
startup phase 4.
The LEDs go off if phase 4 is completed free of errors and then have the significance
according to their definition in normal operation.
Activity
Installing and putting a TIM into operation
5.7 Startup activities of the TIM module
LED 2
LED 3
On
(On)
On
(On)
(On)
(On)
(On)
Flashes
(On)
(On)
(On/flashes)
(On)
(On)
(On/flashes)
(On)
(On)
(On)
(On)
(On)
(On)
Flashes
LED 4
LED 5
On
On
Flashes
On
(On/flashes)
On
(On/flashes)
(On/flashes)
LED 6
On
Flashes
Flashes
225