Siemens SIMATIC NET SINAUT ST7 System Manual page 208

Station control system
Table of Contents

Advertisement

Installing and putting a TIM into operation
5.4 Options for attachment and settings of the TIM 3 and TIM 4 variants
Table 5-39
Pinout of the X3 RJ-45 Western jack for the RS-232/RS-485 port
Illustration
8
7
6
5
4
3
2
1
Interface adapter cable
The connecting cable 6NH7700-0AS05 is supplied with every TIM module that has a second
serial port (combined RS-232/485) instead of an integrated modem. This allows the second
combined RS-232/RS-485 port integrated in the TIM to be connected to an external modem
over the normal connecting cables.
The connecting cable can also be ordered as a spare under the number shown.
Table 5-40
TIM 4R / 4RD interface adapter cable
Order no.
6NH7700-0AS05
The following table shows the pinout of the two connectors for the standard connecting cable
mentioned above.
208
Pin no.
1
2
3
4
5
6
7
8
Description
Adapter cable for connecting the 2nd serial RS-232/485
port integrated in a TIM 4R / 4RD instead of an internal
modem to convert the internal plug (RJ-45) to the 9-pin
D-sub miniature male connector required externally.
Cable length 0.5 m
Signal name
Signal direction
DCD
Input
RXD
Input
TXD
Output
DTR
Output
GND
DSR
Input
RTS
Output
CTS
Input
Pin with 8-pin DIL switch can be
set to RS-485.
Pin with 8-pin DIL switch can be
set to RS-485.
Illustration
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
Remark

Advertisement

Table of Contents
loading