Ctrl.ccrdif1 Current Circuit Failure Protection; Ld0.Tpossltc1 Tap Position; Ld0.Secrsyn1 Synchrocheck Indications; Ld0.Frpfrq1 Frequency Protection (1) - ABB Relion 615 Series Manual

Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 2
IEC 60870-5-103 data mappings
2.3.10
Table 13:

CTRL.CCRDIF1 Current circuit failure protection

IEC 61850 name
SA name
CTRL.CCRDIF1
.Alm.stVal
ALARM
.Op.general
FAIL
2.3.11
Table 14:

LD0.TPOSSLTC1 Tap position

IEC 61850 name
SA name
LD0.TPOSSLTC1
.ValWTr.posVal
TAP_POS
2.3.12
Table 15:

LD0.SECRSYN1 Synchrocheck indications

IEC 61850 name
SA name
LD0.SECRSYN1
.SynPrg.stVal
SYNC_INPRO
.FailCmd.stVal
CMD_FAIL_AL
.FailSyn.stVal
CL_FAIL_AL
.EnSt.stVal
ENERG_STATE
2.3.13
Table 16:

LD0.FRPFRQ1 Frequency protection (1)

IEC 61850 name
SA name
LD0.FRPTRC1
.Str.general
START
LD0.FRPTOF1
.Op.general
OPR_OFRQ
LD0.FRPTUF1
.Op.general
OPR_UFRQ
LD0.FRPFRC1
.Op.general
OPR_FRG
18
CTRL.CCRDIF1 Current circuit failure protection
Description
Fail Alarm
Fail Operate
LD0.TPOSSLTC1 Tap position
Description
Tap position
LD0.SECRSYN1 Synchrocheck indications
Description
Synch in progress
CB close req failed
CB close cmd failed
Line and bus en.state
LD0.FRPFRQ1 Frequency protection (1)
Description
Stage start
Overfrequency
-Operate
Underfrequency
-Operate
Frequency gradient
-Operate
DPI value
FUN
10=Alarm
23
10=Operate
23
DPI value
FUN
Value -64...63
25
DPI value
FUN
10=Progress
26
10=Fail
26
10=Fail
26
Value 0...4
26
DPI value
FUN
10=Start
27
10=Operate
27
10=Operate
27
10=Operate
27
1MRS757055 C
INF
U
ASDU
I
C
1
1
1
1
1
90
1
2
0
1
INF
U
ASDU
I
C
20
1
4
1
-
INF
U
ASDU
I
C
1
1
1
1
1
2
1
1
0
1
3
1
1
0
1
10
1
4
1
-
INF
U
ASDU
I
C
11
1
2
1
1
12
1
2
0
1
13
1
2
0
1
14
1
2
0
1
REU615
Point List Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion reu615

Table of Contents