Switchgear Functions; Ctrl.cxxxxx1 Circuit Breaker - Cb Object And Failure Protection (1); Ctrl.dcxswi1 Disconnector Control (1); Ctrl.dcxswi2 Disconnector Control (2) - ABB Relion REC615 Manual

Grid automation remote monitoring and control
Hide thumbs Also See for Relion REC615:
Table of Contents

Advertisement

1MRS757807 B
2.3.2
2.3.2.1
Table 7:

CTRL.Cxxxxx1 Circuit breaker - CB object and failure protection (1)

IEC 61850 name
CTRL.CBCILO1
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.CBCSWI1
.Pos.stSeld
CTRL.CBXCBR1
.BlkCls.stVal
.BlkOpn.stVal
2.3.2.2
Table 8:

CTRL.DCXSWI1 Disconnector control (1)

IEC 61850 name
CTRL.DCCILO1
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.DCCSWI1
.Pos.stSeld
CTRL.DCXSWI1
.BlkCls.stVal
.BlkOpn.stVal
2.3.2.3
Table 9:

CTRL.DCXSWI2 Disconnector control (2)

IEC 61850 name
CTRL.DCCILO2
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.DCCSWI2
.Pos.stSeld
Table continues on next page
Remote Monitoring and Control REC615
Point List Manual

Switchgear functions

CTRL.Cxxxxx1 Circuit breaker - CB object and failure protection (1)
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN
CTRL.DCXSWI1 Disconnector control (1)
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN
CTRL.DCXSWI2 Disconnector control (2)
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Section 2
DNP3 data mappings
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
19

Advertisement

Table of Contents
loading

Table of Contents