Section 2
DNP3 data mappings
2.3.1.7
Table 10:
CTRL.Exxxxx1 Controllable earth switch (1)
IEC 61850 name
CTRL.ESCILO1
.EnaCls.stVal
.EnaOpn.stVal
.ItlByPss.stVal
CTRL.ESCSWI1
.Pos.stSeld
CTRL.ESXSWI1
.BlkCls.stVal
.BlkOpn.stVal
2.3.1.8
Table 11:
CTRL.CCRDIF1 Current circuit failure protection
IEC 61850 name
CTRL.CCRDIF1
.Alm.stVal
.Op.general
2.3.1.9
Table 12:
LD0.CMHAI1 Power quality - current total demand distortion
IEC 61850 name
LD0.CMHAI1
.Alm.stVal
2.3.1.10
Table 13:
LD0.CMMXU1 Phase currents (1) limit supervision
IEC 61850 name
LD0.CMMXU1
.HiAlm.stVal
.HiWrn.stVal
.LoAlm.stVal
.LoWrn.stVal
18
CTRL.Exxxxx1 Controllable earth switch (1)
SA name
ENA_CLOSE
ENA_OPEN
ITL_BYPASS
SELECTED
BLK_CLOSE
BLK_OPEN
CTRL.CCRDIF1 Current circuit failure protection
SA name
FAIL
ALARM
LD0.CMHAI1 Power quality - current total demand distortion
SA name
ALARM
LD0.CMMXU1 Phase currents (1) limit supervision
SA name
HIGH_ALARM
HIGH_WARN
LOW_ALARM
LOW_WARN
Description
Close enabled
Open enabled
Interlocking bypass
CB selected
Close blocked
Open blocked
Description
Fail Alarm
Fail Operate
Description
Distortion alarm
Description
High alarm
High warning
Low alarm
Low warning
1MRS756711 D
Values
1=Enabled
1=Enabled
1=Bypassed
1=Selected
1=Blocked
1=Blocked
Values
1=Alarm
1=Operate
Values
10=Alarm
Values
1=Alarm
1=Warning
1=Alarm
1=Warning
REF615
Point List Manual