Use this section to enter:
• Modbus communication parameters
• CT (Current Transducer) output voltage and input current ranges
• The service type to be monitored
These instructions assume the meter is set to factory defaults. If it has been previously configured, all optional values should be
checked. For more options (i.e., Potential Transformer ratios, etc.) and the full setup instructions, see the following pages.
A. To Navigate to the Setup screens:
+
1. Press
or
repeatedly until SETUP screen appears.
+
2. Press
to get to the PASWD screen.
3. Press
to move through the digits. Use the
4. Press
to move to the first Setup screen (S COM)
+
5. Use
+
or
to select the parameter screen you want to set.
6. After you set the parameters you want, use
SETUP).
B. To Enter Modbus communication parameters:
1. Navigate to the S COM (set communications) Setup screen (see section A above).
2. Press
to go to the ADDR screen and through the address digits. Use
3. Press
to accept the value and go to the BAUD screen. Use
4. Press
to go to the PAR screen. Use
5. Press
to go back to the S COM screen.
C. To Enter the CT (Current Transducer) output voltage and input current ranges:
1. Navigate to the S CT (Set Current Transducer) Setup screen (see section A above).
2. Press
to go to the CT V screen. Use
3. Press
to go to the CT SZ screen and through the digits. Use
value and
4. Press
to accept the value and go back to the S CT screen.
D. To Enter the service type to be monitored:
1. Navigate to the S SYS (Set System) Setup screen (see section A above).
2. Press
to go to the SYSTM screen. Use
Press
to go back to the S SYS screen. For full setup instructions, see the configuration instructions on the following pages.
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
+
or
buttons to enter your password (the default is 00000).
+
+
or
to select the next Setup screen or
+
+
+
or
+
or
to select the baud rate (default is 19200).
+
+
+
or
to select the parity (default is NONE).
+
+
or
to select the voltage mode Current Transducer output voltage (default is 1.00V).
+
or
to select the CT size in amps (default is 100). accept the
+
+
or
to select the configuration (see wiring diagrams - default is 40).
+
to exit the Setup screens (return to
to select the Modbus address (default is 001).